9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Features, Benefits and Functions
Complete motor protection
and control in a single
compact case reduces
panel space requirements
and wiring costs
Microprocessor design
with self diagnostics
eliminates calibration
and reduces installation,
commissioning and
maintenance
Programmable stop
2–20% of PCT
Intel-I-Trip overload
protection develops
customized curve from
manufacturers supplied
motor data
Intel-I-Trip overload
protection provides
adaptive trip characteristics
based on motor
temperature when motor
RTDs are connected
through an optional
URTD module
Meets UL 1053 ground
fault protection standards
that eliminates the need
for a separate ground relay
saving cost, space, wiring
and time
Voltage dip/loss ride
through capability reduces
unnecessary trips caused
by poor power quality
Motor currents,
temperatures and
conditions are monitored
and displayed either locally
or remotely
Event log provides motor
operating records for the
most recent 20 Trip or
Alarm events with date
and time stamping. This
information can improve
troubleshooting and
reduce downtime
Log book records the most
recent 100 events such as
motor START/STOP and
set point changes to
provide a log of motor
operation with date and
time stamping
RTD diagnostics reduces
unnecessary tripping
caused by faulty RTD, RTD
wiring or communications
Arm/Disarm feature
improves security for
critical motor applications
Motor Start profile verifies
protection and motor
starting coordination. This
feature can be used to
develop protection settings
on old motors where data
is not available
Optional communication
module and Eaton’s
software simplifies setting,
configuration, monitoring,
commissioning and data
retrieval either locally or
remotely
Optional Quick Release
Drawout Case construction
simplifies relay removal
and replacement
The protection functions are
listed below.
I
2
t overload protection
(49/51)
Locked rotor (49S/51)
Ultimate trip current (51)
Negative sequence phase
unbalance (46)
Instantaneous
overcurrent (50)
Ground fault
protection (50G)
RTD trip and alarm with
URTD module (49/38)
Underload trip (37)
Starts per time (66)
Jam or stall (51R)
Auto or manual reset (86)
Fail-safe or non-fail-safe
trip modes
The metering functions are:
Motor currents:
Average current (Iave)
Individual phase and
ground current in
primary amperes
Percent of full load
Percent of phase
unbalance
RTD temperatures:
Individual winding
Motor bearing
Load
Auxiliary temperatures
Motor conditions:
Percent of I
2
t thermal
bucket
Time before start
Remaining starts
allowed
Oldest start time
Standards and Certifications
The MP-3000 motor
protection was designed to
meet the industry standards
for protective relays. It is
recognized under UL 1053
Ground Fault Protection
Standard.
UL recognized
(File No. E154862)
UL 1053 recognized
UL 508 recognized
ANSI C37.90, C37.90.1
cUL
CSA