9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Technical Data and Specifications
Control Power
Control voltage:
48–125 Vac/Vdc
100–240 Vac/Vdc
Operating voltage:
55–264 Vac
38–300 Vdc
Interruption ride-through
time: 20 cycle interruption
of nominal ac supply
Power consumption: 20 VA
maximum
Current Inputs
Nominal (I
n
): 1A or 5A
CT rating:
2 x I
n
continuous
80 x I
n
for 1 second
CT burdens:
< 0.25 VA at 5A
(nominal)
< 0.05 VA at 1A
(nominal)
Voltage Transformer Inputs
Nominal: 120 Vac
Operating range: 69–
150 Vac
Burden:
<0.015 at 120 Vac
1 megaohm
Metering Accuracy
Phase current:
±0.5% or ±0.025A from
0.02–20 per unit fully
offset current waveform
Ground current:
±0.5% of full scale (I
n
)
from 0.02–2.0 per unit
fully offset current
waveform
Phase voltage: ±0.5% or
±0.2V from 0–160 Vac
Frequency measurement
accuracy: ±0.02 Hz
Phase angle: ±1ºC
Power metering accuracy:
±1.5%
Metering accuracy
temperature range: 32ºF to
122ºF (0ºC to 50ºC)
Temperature range: ±5%
for operation below 32ºF
(0ºC) and above 122ºF
(50ºC)
Relay outputs:
2 Form C, NO and NC
5 Form A, NO only
Input signal frequency
necessary for accurate
operation:
60 Hz nominal, 57–63 Hz
(±5%)
50 Hz nominal, 47–53 Hz
(±5%)
Clock accuracy:
Free running ±1 minute/
month at 25ºC
Clock automatically
updated by PowerNet
host when present
Protective Functions
Phase and Ground
Overcurrent Protection
Inverse characteristics:
Mod, Very, Extremely,
IECA, IECB, IECC, It, I
2
t,
I
4
t, Flat
TOC (51) pickup range:
0.1–4.0 per unit in 0.01
steps
Time multipliers: 0.05–10.0
in 0.01 steps
IOC (50) pickup range: 0.1–
20.0 per unit in 0.01 steps
Pickup accuracy: ±1%
(at 0.1–2 per unit)
Time delay: 0–9999 cycles
in 1 cycle steps
Time accuracy: ±3% or
±30 ms
Directional (67, 67N, 67G):
forward, reverse or both
Voltage Unbalance (47)
Threshold (minimum
voltage) 1–100 volts in
1 volt steps
% V2/V1: 4–40% in
1% steps
Time delay: 0–9999 cycles
in 1 cycle steps
Current Unbalance
Threshold (minimum
current) 0.1–20.0 per unit
in 0.01 steps
% I2/I1: 4–40% in
1% steps
Time delay: 0–9999 cycles
in 1 cycle steps
Under/Overvoltage Protection
Pickup range: 10–150 volts
in 1 volt steps
Time delay: 0–9999 cycles
in 1 cycle steps
Under/Over Frequency
Protection
Pickup range: 45–65 Hz in
0.01 Hz steps
Time delay: 0–9999 cycles
in 1 cycle steps
Breaker Failure Protection
Pickup range: 0.1–5.0 per
unit in 0.01 steps
Time delay: 0–9999 cycles
in 1 cycle steps
Power Protection (32)
Forward/reverse:
over/under
Pickup accuracy: ±1.0%
Trip time accuracy:
0 to 12 cycles or 0.1%,
whichever is greater
Sync Check (25)
Phase angle: 1 to 60°C
Slip frequency: 0.1 to 2 Hz
Voltage differential: 1 to
100 volts
Breaker close time: 0 to
9999 cycles
Power Factor
Trigger/reset threshold: 0.5
lag to 0.5 lead in 0.01 steps
Time delay: 0–1000
seconds in 1 second steps
Discrete Inputs
Number of contact
inputs: 8
Rating: 48 Vdc wetting
voltage provided with
internal ground only
Output Contacts
Number of output
contacts: Five Form A and
two Form C
Rating of Output Contacts
Momentary:
Make 30A AC/DC for
0.25
seconds
Break 0.25A at 250 Vdc
(resistive)
Break 5A at 120/240 Vac
Continuous:
5A at 120/240 Vac
5A at 30 Vdc
Logic and Control Functions
Six programmable logic
gates for AND, OR, NAND,
NOR operation
Two latching (flip/flop)
gates
Six timer gates provide
on/off delays
INCOM Communications
Baud rate: 9600 fixed
Maximum distance:
10,000 feet (3,048m)
Protocol: INCOM
RS-485 Communications,
Rear Panel
Baud rate: 19.2K, 9.6K
Protocol: Modbus RTU
RS-232 Communications,
Front Panel
Baud rate: 38.4K, 19.2K,
9.6K
Connector standard 9-pin
subminiature, three-wire
Protocol: INCOM
Environmental Ratings
Operating temperature:
–0ºF to +140ºF (–40ºC to
+60ºC) Product tested to
+185ºF (+85ºC)
Storage temperature:
–40ºF to +185ºF (–40ºC to
+85ºC)
Humidity: 5–95% relative
humidity (noncondensing)
Altitude: 0–6350 feet
(0–1935m) above Mean Sea
Level