User`s guide

Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com V3-T9-175
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Standards and Certifications
Compliance
●
UL Recognized,
File # E154862
●
UL 1053 (1994) recognized
●
ANSI C37.90 (1989)
●
EN 55011 (1991)
●
EN 61000-6-2 (1999)
Emission Tests
●
EN 55011 (1991)—Group 1
Class A (CISPR-11,
Class A)
●
FCC 47 CFR Chapter 1—
Part 15 Subpart b Class A
Immunity Tests
●
ANSI C37.90.1 (1989)—
Surge Withstand Capability
●
ANSI C37.90.2 (1995)—
EMI Immunity to 35V/m
●
EN 61000-4-2 (1995)—
ESD Rating of 8 kV
●
EN 61000-4-3 (1997)—
Radiated EM Field at
10V/m
●
EN 61000-4-4 (1995)—Fast
Transient Burst at 2 kV
●
EN 61000-4-5 (1995)—
Surge Immunity Test
●
EN 61000-4-6 (1996)—
Conducted RF at 10V/m
●
EN 61000-4-11 (1994)—
Voltage Dips and Variations
●
EN 61000-4-8—Power
Frequency Magnetic
Field Immunity
Catalog Number Selection
FP-5000 Feeder Protection
Current Range
2 = 5 Amperes
3 = 1 Ampere
Communications Protocol
0 = INCOM
1 = Modbus
FP5 2 00 - 0 1
Control Voltage
0 = 48–125 Vac/Vdc
1 = 100–240 Vac/Vdc
Packaging
0 = Drawout
1 = Fixed case