9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
The FP-5000 provides the
following metering functions:
●
Amperes (rms, phasor and
sequence)
●
Amperes demand and
peak demand
●
Volts (rms, phasor and
sequence)
●
VA and VA demand
●
Watts and kW demand and
peak demand
●
Forward/reverse/net kWh
●
VARs and kVAR demand
and peak demand
●
Lead/lag/net kVARh
●
Power factor
●
Frequency
●
Voltage and current
●
%THD and magnitude THD
●
Minimum/maximum
recording with date/
time stamp
●
Trending (load profile
over time)
The FP-5000 provides the
following monitoring and data
recording functions that
enhance the security of the
protection system and
provides useful
information
for scheduling maintenance:
●
Trip circuit monitoring
●
Close circuit monitoring
●
Loss-of-vacuum monitoring
●
Breaker wear (accumulated
interrupted current)
●
Waveform capture
(256 cycles total, up to
16 events)
●
Fault data logs (up to
16 events)
●
Sequence of events report
(up to 100 events)
●
Clock
The FP-5000 provides
standard control functions
plus user-configurable
custom control capabilities.
This logic can be used for
applications such as main-tie-
main transfer schemes.
●
Remote open/close
●
Programmable I/O
●
Programmable logic gates
and timers
●
Multiple setting groups
(up to four)
●
Bus transfer logic
●
Cold load pickup
●
Loss of potential
(PT blown fuses)
The FP-5000 supports the
following communication
options:
●
Local HMI
●
Password protected
●
Addressable
●
Local communication port
●
Remote communication
port:
●
FSK
●
RS-232
●
RS-485
●
Protocols:
●
INCOM
●
Modbus
●
Configuration software
Communication Software
Eaton provides two types of
communication software. The
first is PowerPort. It runs on a
PC or laptop for easy access to
a single relay to change set
points or configuration and to
view metered values and
stored data. PowerPort is free
and can be downloaded from
www.eaton.com; search for
‘PowerPort,’ then click the
download search result.
The second package is
PowerNet. PowerNet is a
power management software
package that is designed for
continuous, remote monitoring
of many devices. It provides all
the functionality of PowerPort
plus additional functions such
as billing, trending and
graphics. Contact your local
Eaton representative for more
information on PowerNet
software.
PowerPort and PowerNet Protection Overview Screen