9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Control Power
Control voltage:
48–125 Vdc/100–
120 Vac
100–250 Vdc/100–
240 Vac
Operating voltage:
38–150 Vdc/55–132 Vac
80–308 Vdc/55–264 Vac
Interruption ride-through
time:
83 ms at 120V, 60 Hz AC
250 ms at 110 Vdc/
300 ms at Vac
Power consumption:
20 VA maximum
22 VA maximum
Current Inputs
CT rating:
2 x ln at 5 amperes
continuous
3 x ln at 1 ampere
continuous
80 x ln at 5 amperes
for 1 second
100 x ln at 1 ampere
for 1 second
CT burdens:
< 0.25 VA at 5A
(nominal)
< 0.05 VA at 1A
(nominal)
Voltage Transformer Inputs
Nominal: 0–120 Vac line
to common
Operating range:
0–144 Vac (+20%) line
to common
Burden: 1 mega ohm input
impedance
Metering Accuracy
Input signal frequency
necessary for accurate
operation:
60 Hz Nominal,
57–63 Hz (5%)
50 Hz Nominal,
47–53 Hz (5%)
Frequency measurement
accuracy:
±0.02 Hz
Clock accuracy:
Free running ±1 minute/
month at 77°F (25°C)
Automatically updated
by PowerNet host
when present