9.4
Metering Devices, Protective Relays, Software and Connectivity
Protective Relays
Features, Benefits and Functions
●
Complete protection,
metering and control in
a single compact case to
reduce panel space,
wiring and costs
●
Flexible current, voltage
and frequency protection
and programmability to
cover a broad range of
applications while
simplifying relay ordering
and reducing inventory
●
Integral test function
reduces maintenance
time and expense
●
Relay self-diagnostics and
reporting improves uptime
and troubleshooting
●
Breaker trip circuit
monitoring improves the
reliability of the breaker
operation
●
Programmable LEDs and
logic control features that
can replace and eliminate
external auxiliary relays,
timers, light and wiring
●
Zone selective interlocking
improves coordination and
tripping times and saves
money compared to a
traditional bus differential
scheme
●
Trip and event recording
in non-volatile memory
provides detailed
information for analysis
and system restoration
●
256 cycles of waveform
capture aids in post fault
analysis (viewable using
PowerNet and
NPWAVEFORM
component
●
Front RS-232 port and
PowerPort software
provides local computer
access and a user-friendly,
Windows-based interface
for relay settings, and
configuration and data
retrieval
●
Drawout case design
for quick and easy relay
removal and replacement
●
Breaker open/close
control from relay
faceplate or remotely
via communications
●
Remote communications
to Eaton PowerNet
monitoring system or PC
●
Free PowerPort utility
software for local PC
interface to the FP-6000 for
relay settings, monitoring
and control
The protection functions are
listed below and shown on
Page V3-T9-168.
The FP-6000 provides phase
overcurrent (forward, reverse
or both):
●
Two-stage instantaneous
with timers (50P-1 and
50P-2)
●
Inverse time overcurrent
(51P)
●
Directional control (67P)
●
10 standard curves
●
Instantaneous or time
delay reset
●
Voltage restrained inverse
time overcurrent (51P2)
The FP-6000 provides two
ground overcurrent elements,
one measured (IX) and one
calculated (IR):
●
Independent measured
ground or neutral
directional overcurrent
elements:
●
Two-stage
instantaneous with
timers (50X-1 and 50X-2)
●
Inverse time overcurrent
(51X)
●
Ground directional
polarizing (67N) -3vo and
negative sequence
●
10 standard curves
●
Instantaneous or time
delay reset
●
Independent calculated
ground or neutral
directional overcurrent
elements:
●
Two-stage
instantaneous with
timers (50R-1 and
50R-2)
●
Inverse time overcurrent
(51R)
●
Ground directional
polarizing (67N) –3vo,
I pol and negative
sequence
●
10 standard curves
●
Instantaneous or time
delay reset
The FP-6000 also provides
the following protective
features:
●
Breaker failure (50BF)
●
Phase unbalance negative
sequence overcurrent
(46-1, 46-2)
●
Phase voltage unbalance
and sequence protection
(47-1, 47-2)
●
Main 3-phase under/
overvoltage (27M-1,
27M-2, 59M-1, 59M-2)
●
Under/overfrequency
(81U-1, 81U-2, 81O-1,
81O-2)
●
Auxiliary single-phase
under/overvoltage (27A-1,
27A-2, 59A-1, 59A-2)
●
Neutral voltage (59N-1,
59N-2)
●
Apparent and
displacement power factor
(55A, 55D)
●
Forward/reverse power
protection (32-1, 32-2,
32-3)
●
Forward/reverse VAR
protection (32V-1, 32V-2,
32V-3)
●
Thermal Protection (49DT,
49MT, 49DA, 49MA)
●
Sync check (25)
●
Zone interlocking for bus
protection (87B). The
FP-6000 feeder relay
includes a zone selective
interlocking feature that can
be used with other Eaton
devices like the Digitrip
3000 overcurrent relay
The FP-6000 provides the
following metering functions:
●
Amperes (rms, phasor
and sequence)
●
Amperes demand and
peak demand.
●
Volts (rms, phasor and
sequence).
●
VA and VA demand
●
Watts and kW demand and
peak demand.
●
Forward/reverse/net kWh
●
Vars and kVAR demand
and peak demand
●
Lead/lag/net kVARh
●
Power factor
●
Frequency
●
Voltage and current %THD
and magnitude THD
●
RTD
●
Minimum/maximum
recording with date/
time stamp
●
Trending (load profile
over time)
The FP-6000 provides the
following monitoring and data
recording functions that
enhance the security of the
protection system and
provides useful information
for scheduling maintenance:
●
Trip circuit monitoring
●
Breaker wear (accumulated
interrupted current)
●
Waveform capture
(256 cycles total, up to
16 events)
●
Fault data logs (up to
16 events).
●
Sequence of events report
(up to 100 events)
●
Clock (1ms stamping)
The FP-6000 provides
standard control functions
plus userconfigurable custom
control capabilities. This logic
can be used for applications
such as main-tie-main
transfer schemes.
●
Remote open/close.
●
Optional local open/close
●
Programmable I/O
●
Programmable logic gates
and timers
●
Multiple setting groups
(up to four)
●
Bus transfer logic
●
Cold load pickup
●
Loss of potential
(PT blown fuses)
●
Autoreclose Function (79)
●
Auto Zone Coordination
The FP-6000 supports the
following communication
options:
●
Local HMI
●
Password protected
●
Addressable
●
Front RS-232 port
●
Rear RS-485 port
●
Rear FSK port
●
Protocols:
●
INCOM
●
Modbus RTU