User`s guide

Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com V3-T9-117
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Energy Sentinel
Current Input
Current range: 1% to 125% of current rating
Burden: 1 VA
Voltage Input
Voltage Range: ±20% of voltage rating
Frequency
50 or 60 Hz
Power Factor Range
All (–1 to +1)
Communications
Protocol: INCOM
Speed: 9600 baud
Compatibility: Power Management Software compatible
Environmental Conditions
Operating temperature: –25°C to 70°C
1
(–13°F to 158°F)
Storage temperature: –40°C to 85°C
1
(–40°F to 185°F)
Operating humidity: 5% to 95% relative humidity noncondensing
System Voltage Considerations (Application Note)
The Ground (GND) terminal of the IQ Energy Sentinel should
be connected to the ground bus or other non-current carrying
ground with 600V rated wire to ensure accuracy.
Note
1
40ºC (standard) maximum for Series C circuit breakers.