User`s guide

V3-T9-116 Volume 3—Power Distribution and Control Assemblies CA08100004E—November 2013 www.eaton.com
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9
9.3
Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Product Selection
IQ Energy Sentinels
Technical Data and Specifications
Terminal, Cable and Wiring Guidelines
Description Voltage Rating—Vac
Current Rating
Maximum Amperes
Catalog
Number
For F-Frame breakers 120/240, 240, 208Y/120 150 IQESF208
For F-Frame breakers 220/380, 230/400, 240/415 150 IQESF400
For F-Frame breakers 480, 480Y/277 150 IQESF480
For F-Frame breakers 600, 600Y/347 150 IQESF600
For J-Frame breakers 120/240, 240, 208Y/120 250 IQESJ208
For J-Frame breakers 220/380, 230/400, 240/415 250 IQESJ400
For J-Frame breakers 480, 480Y/277 250 IQESJ480
For J-Frame breakers 600, 600Y/347 250 IQESJ600
For K-Frame breakers 120/240, 240, 208Y/120 400 IQESK208
For K-Frame breakers 220/380, 230/400, 240/415 400 IQESK400
For K-Frame breakers 480, 480Y/277 400 IQESK480
For K-Frame breakers 600, 600Y/347 400 IQESK600
Universal with internal CTs 120/240, 240, 208Y/120 400 IQESUI208
Universal with internal CTs 220/380, 230/400, 240/415 400 IQESUI400
Universal with internal CTs 480, 480Y/277 400 IQESUI480
Universal with internal CTs 600, 600Y/347 400 IQESUI600
Universal for external CTs 120/240, 240, 208Y/120 4000 IQESUE208
Universal for external CTs 220/380, 230/400, 240/415 4000 IQESUE400
Universal for external CTs 480, 480Y/277 4000 IQESUE480
Universal for external CTs 600, 600Y/347 4000 IQESUE600
IQ Energy Sentinels
Sentinel
Eaton’s
Series C Terminal
Wire Size
(Single Conductor)
Wire
Types
F-Frame 624B100G02, G17, G18, G19 #14–1/0, #4–4/0, #4–4/01, #14–1/0 AWG THW, THHN, XHHW
J-Frame T250KB, TA250KB #4–350 kcmil THW, THHN, XHHW
K-Frame T350K, TA350KB #250–500 kcmil THW, THHN, XHHW
Universal Energy Sentinel with internal CTs T350K, TA350KB #250–500 kcmil THW, THHN, XHHW
System Voltage Reference Wiring
Energy Sentinel with internal or external CTs #24–#10 AWG
Current Transformer Wiring
Universal with external CTs #12 AWG (maximum)
Ground Reference Wiring
Energy Sentinel with internal or external CTs #22–#12 AWG (minimum 600 volt rated)
Communications Wiring
Energy Sentinel with internal or external CTs Eaton’s IMPCABLE or Belden 9463 family
F-Frame Eaton’s IMPCABLE or Belden 9463 family
J-Frame Eaton’s IMPCABLE or Belden 9463 family
K-Frame Eaton’s IMPCABLE or Belden 9463 family