Metering Devices, Protective Relays, Software and Connectivity
Metering Devices
Technical data and Specifications
External Circuit Group Specifications
PXMP-MB (-AB) Meter base
Discrete Output
Quantity 1—solid-state relay Form A NO Bidirectional FET
Polarity of external source is not important
Isolation circuit to ground 2 kV/1 min.
Maximum external source voltage 28 Vdc
Line-to-line TVS clamp across switching element at 32 Vdc
Solid-state relay on resistance 35 ohms maximum
Maximum load current 80 mA
Minimum pulse width 20 milliseconds
Fixed 25 milliseconds for pulse initiator function
Maximum pulse rate 25 Hz
Wiring to two-position removable terminal plug
12–18 AWG (3.31–0.82 mm2), wire ferrules recommended
T1 (polarity not important)
T2 (polarity not important)
Discrete Inputs
Quantity 3, common circuits inputs 1–3
Group isolation 2 kV
No input-to-input circuit isolation
All inputs per module share a common external
24V (±10%) supply
24V externally sourced between common and inputs
Design to interface with external dry contact
Input impedance ~2.2K ohms
Input current draw ~10 mA per input
Minimum pulse width 10 milliseconds
Maximum pulse rate 20 Hz
Wiring to four-position removable terminal plug
12–18 AWG (3.31–0.82 mm2), wire ferrules recommended
T3—Common (connect ext. 24 common here)
T4—Input 1 (dry contact to 24V hot)
T5—Input 2 (dry contact to 24V hot)
T6—Input 3 (dry contact to 24V hot)
COM1 and COM2 RS-485 Serial Ports
No D+/D– biasing reliance on fail-safe driver and biasing at
Master
Baud rate configurable between 9600–115K baud (default)
Use cable designed for RS-485 communications
Low L:L capacitance
Impedance of ~100–120 ohms
Shield—Mylar for high frequency; Braid for low frequency
Separate common and shield for best noise immunity
Maximum cable length is 4000 ft (1219.2m) with 32 nodes
at 19.2K baud increased data rates will reduce maximum
cable distance
2000 ft (609.6m) with 32 total nodes at 115.2K baud
Isolation 300V to ground due to TVS diode clamps
Modbus RTU slave protocol, address defined by rotary switch
Green Rx and Red Tx LEDs per channel
Data + > Data—during idle marked, logic 1 state
End of Line Termination resistance should match cable
impedance (typ. 100–120 ohms)
Four-position removable terminal plug 18–22 AWG (0.82–0.33
mm
2
) typical, wire ferrules recommended
COM1
T7—Shield
T8—RS-485 common
T9—Data –
T10—Data +
COM2
T11—Shield
T12—RS-485 common
T13—Data –
T14—Data +
PXMP-MB Power Supply Input
24 Vdc ±20%
15W maximum load
1 kV isolation barrier internal to PXMP-MB
Externally fuse circuit to protect wire
Green power OK LED
Three-position terminal block 16–12 AWG (1.31–3.31 mm2),
wire ferrules recommended
T15—24 Vdc – (common)
T16—24 Vdc + (Hot)
T17—Shield (optional) capacitively referenced to chassis
ground for enhanced EMC performance
Meter Voltage Inputs
Overvoltage CAT III
Maximum voltage rating
480VL:G (corner grounded delta)
347VL:N
600VL:L
Frequency rating 47–63 Hz
Metering range (temporary transitions)
30–700VL:N
30–700VL:L
Abuse withstand rating 1000V sustained
High pot withstand rating 2500V/1min
Input impedance 4M ohms
Fuse inputs rated to protect wiring to mains. External fuses
must be installed between the meter voltage terminal and the
mains disconnect switch to the main lines to protect the lines.
600V 1 A BUSS type KTK-R-1 Fast Acting or equivalent fuses
are recommended.
Wiring to removable terminal plug 10–18 AWG (5.26–0.82
mm
2
), wire ferrules recommended
T18—N (VR)
T19—C (V3)
T20—B (V2)
T21—A (V1)