Datasheet

03/21/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 4
2 x (1…2.5)
Flexible with ferrule to DIN 46228
mm
2
1 x (1…2.5)
2 x (1…2.5)
Solid or stranded AWG 18…14
Specified tightening torque for terminal screws
Main cable Nm 1.7
Control circuit cables Nm 1
Main�conducting�paths
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated operational voltage U
e
V
AC
690
Rated uninterrupted current = rated operational current I
u
= I
e
A 32
Rated frequency f Hz 40 - 60
Current heat loss (3 pole at operating temperature) W 6
Lifespan, mechanical Operations x
10
6
0.05
Lifespan, electrical (AC-3 at 400 V) Operations x
10
6
0.05
Maximum operating frequency Ops./
h
Max. operating frequency Ops/
h
60
Motor switching capacity kA
rms
AC-3 (up to 690 V) A 32
Trip�blocks
Temperature compensation °C -5 – 40 (to IEC/EN 60947, VDE 0660)
-25 – 55 (operating range)
Temperature compensation residual error for T > 40 °C
0.1%/K
Setting range of overload releases 0.25 - 1 x I
u
Fixed short-circuit release Basic device 14 x I
u
Short-circuit release tolerance ± 20%
Phase-failure sensitivity yes
Technical�data�according�to�ETIM�4.0
Rated operation power at AC-3, 400 V kWh 0
With integrated auxiliary switch No
Rated permanent current Iu A 32
With integrated under voltage release No
Number of poles 3
Degree of protection (IP) IP20
Connection type main current circuit Screw connection
Characteristics