Datasheet

03/21/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 4
PKE32�basic�device
Part�no. PKE32
Article�no. 121722
Program
Single unit/Complete unit Element
Setting range of useable overload releases I
r
CSA 8 - 32
Setting range of overload releases I
r
A 8–32
Function Without overload releases
Motor output/rated motor current
Motor
rating
AC-3
rated
motor
current
220, 230
240 V
380, 400,
415 V
440 V 500 V 660, 690 V
P [kW] I [A] I [A] I [A] I [A] I [A]
2.2 8.7
3 11.5
4 14.8 8.5
5.5 19.6 11.3 10.2 9
7.5 26.4 15.2 13.8 12.1 8.8
11 21.7 19.8 17.4 12.6
15 29.3 26.6 23.4 17
18.5 28.9 20.9
22 23.8
30 32
Approbationen
UL approval Yes
CSA approval Yes
Product Standards UL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE marking
NA Certification Request filed for UL and CSA
Specially designed for NA No
General
Standards IEC/EN 60947, VDE 0660
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C
Storage °C -20 - +80
Open °C -20 - +55
Enclosed °C -20 - +40
Mounting position
Direction of incoming supply as required
Degree of protection
Device IP20
Terminations IP00
EN50274 busbar tag shroud Finger and back-of-hand proof
Mechanical shock resistance half-sinusoidal shock 10 ms to IEC
60068-2-27
g 25
Altitude m 2000
Terminal capacity screw terminals
mm
2
Solid
mm
2
1 x (1 - 6)
2 x (1 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 6)
2 x (1 - 6)
Solid or stranded AWG 18 - 10
Terminal capacity springloaded terminals
Solid
mm
2
1 x (1…2.5)

Summary of content (4 pages)