Datasheet

03/26/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 4
DC x U
s
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 63
Voltage per contact pair in series V 60
DC-23A, motor load switchL/R = 15 ms
24 V
Rated operational current I
e
A 50
Contacts Quantity 1
48 V
Rated operational current I
e
A 50
Contacts Quantity 2
60 V
Rated operational current I
e
A 50
Contacts Quantity 3
120 V
Rated operational current I
e
A 25
Contacts Quantity 3
Notes
Notes�Main switch characteristics to IEC/EN 60204; positive opening of contacts, operator element positively located on shaft
The rated uninterrupted current I
u
is stated at max. connected cross-section.
For terminal capacity solid, stranded and flexible:
Max. 2 cross-section sizes difference admissible when using 2 conductors.
Technical�data�according�to�ETIM�4.0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Rated permanent current Iu A 63
Number of poles 3
Conditioned rated short-circuit current Iq kA 0
Degree of protection (IP), front side IP65
Number of auxiliary contacts as change-over contact 0
Interlockable No
Motor drive integrated No
Connection type main current circuit Screw connection
Version as emergency stop installation No
Type of control element Toggle
Version as main switch No
Version as switch disconnector compact YES
Version as safety switch No
Version as maintenance-/service switch No
Rated operation power at AC-23, 400V kWh 37
Rated operation power AC-3, 400 V kWh 30
Suitable for ground mounting No
Suitable for front mounting YES
Suitable for front mounting center No
Suitable for distribution board installation No
Suitable for intermediate mounting No
Max. rated operation voltage Ue AC V 690
Motor drive optional No
Voltage release optional No
Device construction Built-in device fixed built-in technique
Characteristics
Form for ordering non-standard front plates