Datasheet
03/21/2012 HPL-ED2011 V2.0 EN (UX111) 3 / 6
220/230 V P kW 7.5
400 V P kW 13
500 V P kW 15
690 V P kW 12
AC-23A Motor load switches (main switches maintenance switches) P kW
230 V P kW 8.5
400 V P kW 15
500 V P kW 18.5
690 V P kW 17.5
DC x U
s
DC-1, Load-break switches L/R = 1 ms
Rated operational current I
e
A 32
Voltage per contact pair in series V 60
DC-23A, motor load switchL/R = 15 ms
24 V
Rated operational current I
e
A 25
Contacts Quantity 1
48 V
Rated operational current I
e
A 25
Contacts Quantity 2
60 V
Rated operational current I
e
A 25
Contacts Quantity 3
120 V
Rated operational current I
e
A 12
Contacts Quantity 3
Auxiliary�contacts
Standards According to IEC/EN 60204-1, VDE 0113 Part 1
Notes
Notes�Main switch characteristics to IEC/EN 60204; positive opening of contacts, operator element positively located on shaft
The rated uninterrupted current I
u
is stated at max. connected cross-section.
For terminal capacity solid, stranded and flexible:
Max. 2 cross-section sizes difference admissible when using 2 conductors.
Technical�data�according�to�ETIM�4.0
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Rated permanent current Iu A 32
Number of poles 3
Conditioned rated short-circuit current Iq kA 0
Degree of protection (IP), front side IP65
Number of auxiliary contacts as change-over contact 0
Interlockable YES
Motor drive integrated No
Connection type main current circuit Screw connection
Version as emergency stop installation YES
Type of control element -
Version as main switch YES
Version as switch disconnector compact YES
Version as safety switch No
Version as maintenance-/service switch YES
Rated operation power at AC-23, 400V kWh 15
Rated operation power AC-3, 400 V kWh 13
Suitable for ground mounting YES
Suitable for front mounting No
Suitable for front mounting center No