03/21/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 6
Product Standards UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94; IEC/EN 60947-3; CE marking
UL File No. E36332
UL CCN NLRV
CSA File No. 12528
CSA Class No. 3211-05
NA Certification UL listed, CSA certified
Specially designed for NA Yes, in combination with "+NA-I2" (105866)
Suitable for Branch circuits, suitable as motor disconnect
Degree of Protection IEC: IP65; UL/CSA Type 3R, 12
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA,
UL switch disconnector according to IEC/EN 60947-3
Lifespan, mechanical Operations x
10
6
0.3
Maximum operating frequency Operations/
h
50
Climatic proofing Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclical, to IEC
60068-2-30
Ambient temperature °C
Open °C - 25 - 50
Enclosed °C - 25 - 40
Mounting position As required
Mechanical shock resistance to IEC 60068-2-27 Half-
sinusoidal
shock
20 ms
g > 15
Contacts
Rated operational voltage U
e
V
AC
690
Rated impulse withstand voltage U
imp
V
AC
6000
Overvoltage category/pollution degree III/3
Rated uninterrupted current I
u
A
open I
u
A 32
Enclosed I
u
A 32
Load rating with intermittent operation, class 12
AB 25 % DF x I
e
2
AB 40 % DF x I
e
1.6
AB 60 % DF x I
e
1.3
Short-circuit rating
Fuse A
gG/
gL
50
Rated short-time withstand current (1 s current) I
cw
A
rms
640
Switching angles ° 90
Current heat loss per contact at I
e
W 1.8
Terminal�capacities
Solid or stranded
mm
2
1 x (1.5 - 6)
2 x (1.5 - 6)
Flexible with ferrule to DIN 46228
mm
2
1 x (1 - 4)
2 x (1 - 4)
Terminal screw M4
Tightening torque Nm 1.6
Switching�capacity
AC x U
s
Rated making capacity cos ϕ = 0.35 A 320
Rated breaking capacity, motor load switch cos ϕ = 0.35 A
230 V A 260
400 V A 300
500 V A 290
690 V A 250
Rated operational current 440 V load-break switch AC-21A I
e
A 32
Rating, AC-3 motor load switch P kW