User`s guide

SHUTDOWN
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
80
t
Power Restoration Before End of Shutdown Duration
If power is restored before the end of the Shutdown Duration, the UPS is shut off
after the Shutdown Duration for a time equal to the forced reboot delay (10 seconds).
Figure 58 shows a graph of a power restoration before the end of the Shutdown
Duration.
Shutdown
Duration
Utility
Failure
Start Shutdown
Output 1
Start Shutdown
Main Output
Utility
Restore
Utility
Main Output
Output 1
NetWatch/NSM 1 on Main Output
NetWatch/NSM 2 on Output 1
Shutdown Duration
Output 1
Battery Capacity Under
(Output 1)
Battery
Capacity Under
Forced
Reboot
Figure 58. Power Restoration Before End of Shutdown Duration
Shutdown Management With Two ConnectUPS-MS Cards
Some UPSs can have two ConnectUPS-MS Cards to:
S Increase the number of protected servers
S Protect two groups of servers connected to separate networks
Shutdown Duration
The protection application transmits its own shutdown duration to the
ConnectUPS-MS Card (as described in Table 17). Based on these values (maximum
shutdown duration of all subscribed customer systems), the card sends the delayed
shutdown order to the UPS. If the UPS has two ConnectUPS-MS Cards, the
maximum shutdown duration of the two groups of protected systems is used for the
delayed shutdown order.
For example, if the subscribed customers of the first ConnectUPS-MS Card have a
maximum shutdown duration of 60 seconds and the customers of the second
ConnectUPS-MS Card have a maximum shutdown duration of 120 seconds, the
server's shutdown will be launched 120 seconds before the UPS powers down.