User`s guide
SHUTDOWN
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
78
t
Load Shedding or Sequential Shutdown
You can optimize backup time by shutting down non-priority equipment or sequencing
the shutdown of several devices.
Two shutdown criteria are possible:
S Shutdown of receptacles after a set battery back-up time (After)
S Shutdown of receptacles at a given battery discharge level (if battery capacity
under)
If you specify values for both criteria, the first criterion reached initiates server
shutdown.
Sequential Startup
You can delay receptacle power-on to reduce inrush currents on startup or to
sequence the startup of several devices.
Load segment startup after a given time is based on startup of the main receptacle.
Extended Power Outage, Shutdown Initiated by the Shutdown Timer (Shutdown After)
During battery backup time, the Shutdown Timer of the ConnectUPS-MS Card is
reached. After a user-defined backup time period (see “Shutdown Parameters” on
page 31), the shutdown of all servers is initiated, followed by the UPS shutdown
(depending on its configuration). The UPS restarts when utility power is restored
(depending on its configuration).
Shutdown duration: Maximum value of shutdown times of the protection application
subscribed to the card. This value is updated each time a client subscribes or
unsubscribes. Figure 56 shows a graph of a shutdown initiated by the Shutdown
Timer.
Shutdown Duration
Main Output
Utility
Failure
Start Shutdown
Output 1
Start Shutdown
Main Output
Utility
Restore
Utility
Main Output
Output 1
NetWatch/NSM 1 on Main Output
NetWatch/NSM 2 on Output 1
Shutdown After 1
Shutdown Duration
Output 1
Shutdown After
Figure 56. Shutdown Initiated by Shutdown Timer