User`s guide
MIB OBJECTS
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
63
t
Eaton Pulsar MIB
This section contains an overview of MIB definitions for the following MIB files:
S Eaton Pulsar MIB (MGE MIB)
S Eaton Pulsar MIB (MGE MIB) for EMPs
The ConnectUPS-MS Card implements the reduced Eaton Pulsar MIB (MGE MIB);
only the objects listed in Table 12 and Table 13 are managed. The entire MIB
description is available at www.eaton.com/powerquality.
Table 13 lists objects that are managed if there is an optional Environmental
Monitoring Probe (EMP) installed. The Eaton Pulsar MIB trap access path is
1.3.6.1.4.1.705.1.
Table 12. Eaton Pulsar MIB (MGE MIB) Objects
MIB Object SNMP Format Add.path
upsmgIdentFamilyName String {1,1,0}
upsmgIdentModelName String {1,2,0}
upsmgIdentFirmwareVersion String {1,4,0}
upsmgIdentSerialNumber String {1,7,0}
upsmgConfigLowBatteryTime seconds {4,7,0}
upsmgConfigLowBatteryLevel % {4,8,0}
upsmgConfigAutoRestart 1 (yes), 2 (no) {4,9,0}
upsmgConfigVARating VA {4,12,0}
upsmgBatteryRemainingTime seconds {5,1,0}
upsmgBatteryLevel % {5,2,0}
upsmgBatteryVoltage deciVolts {5,5,0}
upsmgBatteryCurrent deciAmps {5,6,0}
upsmgBatteryFaultBattery 1 (yes), 2 (no) {5,9,0}
upsmgBatteryReplacement 1 (yes), 2 (no) {5,11,0}
upsmgBatteryLowBattery 1 (yes), 2 (no) {5,14,0}
upsmgBatteryChargerFault 1 (yes), 2 (no) {5,15,0}
upsmgBatteryLowCondition 1 (yes), 2 (no) {5,16,0}
upsmgInputPhaseNum — {6,1,0}
mginputVoltage_1 DeciVolts {6,2,1,2,1,0}
mginputVoltage_2 DeciVolts {6,2,1,2,2,0}
mginputVoltage_3 DeciVolts {6,2,1,2,3,0}
mginputFrequency_1 DeciHz {6,2,1,3,1,0}
mginputFrequency_2 DeciHz {6,2,1,3,2,0}
mginputFrequency_3 DeciHz {6,2,1,3,3,0}
mginputMinimumVoltage — {6,2,1,4,0}
mginputMaximumVoltage — {6,2,1,5,0}
mginputCurrent_1 DeciAmps {6,2,1,6,1,0}
mginputCurrent_2 DeciAmps {6,2,1,6,2,0}