CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
57
t
View Environment Log Data
The Environment Log Data page displays the recorded date, time, temperature, and
humidity measurements (see Figure 42).
Figure 42. Environment Log Data Page
Temperature and humidity measurements are recorded at an interval defined on the
Environment log interval on the System Settings page (see “System Settings”on
page 42). By default, this period is 300 seconds.
Each measurement is dated and stored in the log of the UPS’s communication card.
The size of log files is limited by a time indexing system.
You can save the log in a CSV format file to your workstation at any time.
You can also clear the files contained in the card to reset the log.