User`s guide
CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
56
t
S Hysteresis (temperature): Hysteresis must be set to prevent multiple notifications if
temperature fluctuates around a threshold. The default value is 2°C / -3.6°F.
The high alarm disappears when the value drops below the high threshold minus
hysteresis value.
The low alarm disappears when the value returns above the low threshold plus the
hysteresis value.
S High threshold (humidity): If the humidity exceeds the set threshold, a notification is
triggered if enabled. The default value is 90%.
S Low threshold (humidity): If the humidity falls below the set threshold, a notification
is triggered if enabled. The default value is 5%.
S Hysteresis (humidity): Hysteresis must be set to prevent multiple notifications if
humidity fluctuates around a threshold. The default value is 5%.
The high alarm disappears when the value drops below the high threshold minus
the hysteresis value.
The low alarm disappears when the value returns above the low threshold plus the
hysteresis value.
S Input #1 and Input #2: An identifier corresponding to the acquired contact (for
example: rack door, air conditioning, or generator unit). The maximum length is
28 characters.
S when closed and when open: The names associated with the two contact positions
(for example "open" and "closed" for a door, "on" and "off" for a generator).
S Notification: Notification of each status change if enabled. When the Notification
box is selected, the following functions are activated for each event selected:
- Display in the list of current alarms
- Consideration in the UPS log
- SNMP trap generation
- Notification by e-mail. The Environment Log check box must be selected on the
Email Notification page. See “E-Mail Notification“ on page 36.
NOTE See Table 9 on page 26 for a list of alarm messages.
S System Shutdown: Selection triggers a system shutdown for each selected
notification. This option is available only for parameters that have Notification
selected.
S Show advanced parameters: Selection displays the Hysteresis parameters and
system shutdown options.