CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
50
t
S SNMP Version: This field allows the user to select the SNMP protocol version:
{Disabled, V1, V3 are supported by the card}.
S SNMP Community Read-Only: Provides the SNMPv1 Read community name
that identifies a sub-group attached to a network manager or a logical entity. The
card and the clients must share the same community name to communicate.
S SNMP Write Enabled: Enables the SNMP write function.
S SNMP Community Write: Displays only if SNMP Write is enabled. The SNMPv1
Write community name that identifies a sub-group attached to a network manager
or a logical entity. The card and the clients must share the same community name
to communicate.
S Read-Only User: Identifies the login of the user in the SNMPv3 version, which is
authorized to read only SNMP variables.
S The Read-Only Security Level: Selects the security level:
- No Auth No Priv: the user must not use authentication and privacy to access to
SNMP variables.
- Auth No Priv: the user must use authentication and NOT privacy to access to
SNMP variables.
- Auth Priv: the user must use authentication and privacy to access to SNMP
variables.
S The Read-Only Password: Allows administrators to specify a new password for
the Read-Only User. Its length must range between 8 and 24 characters and use
only letters, numbers, and <>&@#%_=:;,./?|$*() symbols.
S Read-Write User: Identifies the login of the user in the SNMPv3 version, which is
authorized to read and write SNMP variables.
S The Read-Write Security Level: Selects the security level:
- No Auth No Priv: the user must not use authentication and privacy to access to
SNMP variables.
- Auth No Priv: the user must use authentication and NOT privacy to access to
SNMP variables.
- Auth Priv: the user must use authentication and privacy to access to SNMP
variables.
S The Read-Write Password: Allows administrators to specify a new password for
the Read-Write User. Its length must range between 8 and 24 characters and use
only letters, numbers, and <>&@#%_=:;,./?|$*() symbols.
S The Notification username: Allows administrators to specify the “username”
field for SNMPv3 notifications. IThis field has to be defined in the applications that
recieved those notifications.
S Save: Saves any modifications.