User`s guide

CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
32
t
UPS Shutdown (Master)
S Shutdown if Remaining time under: Values are 0 to 99999 seconds (180 by default).
This value is the minimum remaining backup time before the shutdown sequence
is launched.
S Shutdown if Capacity is under: (Advanced parameter.) Values are 0 to 100%. The
percentage cannot be less than that of the UPS and is the minimum remaining
battery capacity level before the shutdown sequence launches.
S Shutdown after: (Advanced parameter.) Values are 0 to 99999 minutes, not validated
by default. This value is the operating time in minutes left for users after a switch
to backup before starting the shutdown sequence.
S Shutdown duration The default values is 120 seconds. This value is the time
required for complete shutdown of systems when a switch to backup time is long
enough to trigger the shutdown sequences. It is calculated automatically at the
maximum of Shutdown duration of subscribed clients, but can be modified in the
Advanced mode.
S Restart If Capacity exceeds: (Advanced parameter.) This value is the minimum
battery level to reach before restarting the UPS after utility is restored.
Load Segments Shutdown (Group 1 and Group 2)
NOTE Some UPSs do not support the load segments control feature.
To program the operation time and level in backup mode to manage receptacle load
shedding in the event of electric power failure, set the following parameters:
S Switch Off after: Values are 0 to 99999 seconds (default is 65535 seconds). The
time during which the load segment is supplied, starting from the moment of utility
failure.
NOTE The Switch Off after time includes the load segment shutdown duration.
S Switch Off if Capacity under: (Advanced parameter.) Default is 0%. An extra
condition for load segment shutdown that can trigger the shutdown sequence
before the shutdown duration runs out.
S Shutdown duration: The time required for complete shutdown of the systems
supplied by the load segment when a load segment shutdown sequence launches.
Time can be modified in the Advanced mode.
S Switch On after: Values are 0 to 99999 seconds (default is 65535 seconds). The
period between main output startup and startup of the relevant programmable load
segment; therefore load segment startup can be delayed in relation to the main
output.
NOTE Some UPSs do not support the Switch On after option.