User`s guide
CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
31
t
Shutdown Parameters
Select Shutdown Parameters from the menu bar to view and configure UPS operating
parameters in battery mode and for power restoration (see Figure 24).
Figure 24. Shutdown Parameters Page (Advanced Parameters Shown)
Click Show advanced parameters to display additional parameters for adjusting specific
thresholds related to the percentage of remaining battery charge level.
The Output column allows you to name each receptacle (maximum 20 characters).
Since priority is given to the main receptacle, the card cannot supply power to the
load segments when the main receptacle power is off.
NOTE For security purposes, the administrator must click Save and enter the admin user name and
password to save modifications or run commands. The default user name and password are both
admin.