User`s guide
CONFIGURING THE CARD
Eaton ConnectUPS –MS Web/SNMP Card S 164201819 Rev 3 www.eaton.com/powerquality
29
t
UPS Control
Select UPS Control from the menu bar to open the UPS Control page (see Figure 22).
NOTE The UPS Control page requires that you are logged in. If you are not logged in when you select UPS
Control, the Login window opens (see “Logging In” on page 16).
Figure 22. UPS Control Page
The UPS Control page enables triggering of startup and shutdown sequences for the
UPS main output and load segments.
The status of each output displays by a icon associated with the Off label (red icon) or
On label (green icon).
The shutdown sequences allow time for the registered servers to shut down without
losing data (see “Shutdown Parameters” on page 31).
The Master has priority over the load segments. Shutdown of the Master causes the
load segments to shut down. Load segments can be started only if the Master is on.
The list in the Control column displays the following commands, which are initialized
by clicking Execute. These commands include:
S Safe power down: Immediately launches a sequence to switch off output power.
The command shuts down the supplied systems while the shutdown sequence
runs, then switches off the output.
S Safe power down & reboot: Immediately launches a sequence to switch off and then
restore output power. It shuts down the powered systems during the shutdown
sequence, and then switches off the output. Finally, it launches the restart
sequence at the end of the time delay specified in the Toggle duration parameter.
The output status is updated.
S Immediate On: Immediately launches a sequence to switch on output power. The
output is re-powered. This command can start the system if the system's basic
input/output system (BIOS) settings allow a reboot.
S Delayed, safe power down: This is the same switch off sequence as for the Safe
power down command, but postponed by the number of seconds programmed in
the Off Delay parameter.