User`s guide

MIB Objects
Eaton Network Card-MS User’s Guide P-164000100—Rev 1 www.eaton.com/powerquality 68
Traps
Traps are sent on status transition (when an alarm appears or disappears). Traps are composed of three levels
and can be filtered for severity:
l
Level 1: Warning
l
Level 2: Severe
l
Level 3: Critical
See Table 25 for a list of the main managed traps and Table 15 for a list of additional traps that are managed if
there is an optional EMP installed.
The trap access path is 1.3.6.1.4.1.705.1.11.
upsmgEnvironmentTemperature 0.1° C {8,7,1,3,1}
upsmgEnvironmentTemperatureLow 1 (yes), 2 (no) {8,7,1,4,1}
upsmgEnvironmentTemperatureHigh 1 (yes), 2 (no) {8,7,1,5,1}
upsmgEnvironmentHumidity 0.1% {8,7,1,6,1}
upsmgEnvironmentHumidityLow 1 (yes), 2 (no) {8,7,1,7,1}
upsmgEnvironmentHumidityHigh 1 (yes), 2 (no) {8,7,1,8,1}
upsmgEnvironmentInput1State closed (1), open (2) {8,7,1,9,1}
upsmgEnvironmentInput2State closed (1), open (2) {8,7,1,10,1}
Table 24. Pulsar MIB (MGE MIB) Objects (EMPs) (Continued)
MIB Object SNMP Format Add.path
NOTE See “Notified Applications” on page 40 to set the trap severity.
Table 25. MIB Traps
MIB Trap Trap Trap Severity Level
upsmgBatteryFault 1 3
upsmgBatteryOK 2 1
upsmgAtLowBattery 5 3
upsmgFromLowBattery 6 1
upsmgChargerFault 7 3
upsmgChargerOK 8 1
upsmgOnBattery 11 2
upsmgReturnFromBattery 12 1
upsmgOnByPass 13 2
upsmgReturnFromByPass 14 1
upsmgUtilityFailure 17 2
upsmgUtilityRestored 18 1
upsmgOverLoad 21 3
upsmgLoadOK 22 1
upsmgOverTemperature 23 3
upsmgTemperatureOK 24 1