User`s guide

MIB Objects
Eaton Network Card-MS User’s Guide P-164000100—Rev 1 www.eaton.com/powerquality 66
Eaton Pulsar MIB
This section contains an overview of MIB definitions for the following MIB files:
l
Eaton Pulsar MIB (MGE MIB)
l
Eaton Pulsar MIB (MGE MIB) for an Environmental Monitoring Probe (EMP)
The Network Card-MS implements the reduced Eaton Pulsar MIB (MGE MIB); only the objects listed in
Table 23 and Table 24are managed. The entire MIB description is available at www.eaton.com/powerquality.
Table 24 lists objects that are managed if there is an optional EMP installed. The Eaton Pulsar MIB trap access
path is 1.3.6.1.4.1.705.1.
xupsTopoMachineCode Integer {13.2.0}
xupsTopoUnitNumber Integer {13.3.0}
xupsTopoPowerStrategy Integer {13.4.0}
Table 23. Eaton Pulsar MIB (MGE MIB) Objects
MIB Object SNMP Format Add.path
upsmgIdentFamilyName String {1,1,0}
upsmgIdentModelName String {1,2,0}
upsmgIdentFirmwareVersion String {1,4,0}
upsmgIdentSerialNumber String {1,7,0}
upsmgConfigLowBatteryTime seconds {4,7,0}
upsmgConfigLowBatteryLevel % {4,8,0}
upsmgConfigAutoRestart 1 (yes), 2 (no) {4,9,0}
upsmgConfigVARating VA {4,12,0}
upsmgBatteryRemainingTime seconds {5,1,0}
upsmgBatteryLevel % {5,2,0}
upsmgBatteryVoltage deciVolts {5,5,0}
upsmgBatteryCurrent deciAmps {5,6,0}
upsmgBatteryFaultBattery 1 (yes), 2 (no) {5,9,0}
upsmgBatteryReplacement 1 (yes), 2 (no) {5,11,0}
upsmgBatteryLowBattery 1 (yes), 2 (no) {5,14,0}
upsmgBatteryChargerFault 1 (yes), 2 (no) {5,15,0}
upsmgBatteryLowCondition 1 (yes), 2 (no) {5,16,0}
upsmgInputPhaseNum {6,1,0}
mginputVoltage_1 DeciVolts {6,2,1,2,1,0}
mginputVoltage_2 DeciVolts {6,2,1,2,2,0}
mginputVoltage_3 DeciVolts {6,2,1,2,3,0}
mginputFrequency_1 DeciHz {6,2,1,3,1,0}
mginputFrequency_2 DeciHz {6,2,1,3,2,0}
mginputFrequency_3 DeciHz {6,2,1,3,3,0}
mginputMinimumVoltage {6,2,1,4,0}
mginputMaximumVoltage {6,2,1,5,0}
Table 22. PowerMIB Objects (Continued)
MIB Object SNMP Format Add.path