User`s guide
Using the Telnet/SSH/CLI Interface
Eaton Network Card-MS User’s Guide P-164000100—Rev 1 www.eaton.com/powerquality 62
Default Login/Password
If the login or password is lost, select the “Set login password to default” menu option to enable the default
Login/Password.
Default Configuration
Use the “Default configuration” menu option to enable the default configuration. The Network Card-MS
automatically restarts after the default configuration is enabled.
Example #> getHum Offset
setHum To modify a humidity setting
Syntax setHum [option1] [option2] ...
Options HighThreshold = xx
LowThreshold =xx
Hysteresis = xx (0..5)
Offset = xx (-5..5)
HighNotify = 0|1 (0=No, 1=Yes)
LowNotify = 0|1 (0=No, 1=Yes)
HighShutdown = 0|1 (0=No, 1=Yes) (NOTE 1)
LowShutdown = 0|1 (0=No, 1=Yes) (NOTE 1)
Example #> setHum HighNotify=0
Comments (NOTE 1) : Writing enabled only if the notification is enabled
getInput1 or getInput2 To read input setting
Syntax getInput1 [option1] [option2] ...
Options iName
State[0].Description
State[0].Notify
State[0].Shutdown
State[1].Description
State[1].Notify
State[1].Shutdown
Example #> getInput1 iName
getInput1 or serInput2 To modify input setting
Syntax setInput1 [option1] [option2] ...
Options iName = “xx..xx”
State[0].Description = “xx..xx”
State[0].Notify = 0|1 (0=No, 1=Yes)
State[0].Shutdown = 0|1 (0=No, 1=Yes)
State[1].Description = “xx..xx”
State[1].Notify = 0|1 (0=No, 1=Yes) (NOTE 1)
State[1].Shutdown = 0|1 (0=No, 1=Yes) (NOTE 1)
Example #> setInput1 State[0].Label = “Door open” State[0].Notify = 1
Comments (NOTE 1) : Writing enabled only if the notification is enabled
Table 21. Environment Commands (Continued)