Datasheet
03/22/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 5
Electromagnetic fields (RFI), to IEC EN 61000-4-2 V/m 10
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)
Supply cables kV 2
Signal lines kV 2
Power pulses (surge) (IEC/EN 61000-4-5) kV 2 (supply cables, symmetrical)
power pulses (surge) (IEC/EN 61000-4-5, level 2) kV 0.5 (supply cables, symmetrical)
Radiated RFI (IEC/EN 61000-4-6) V 10
Insulation�resistance
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance EN 50178
Digital�inputs�24�V�DC
Number 6
Inputs can be used as analog inputs 2 (I11, I12)
Potential isolation
From power supply No
Between digital inputs No
From the outputs Yes
to PC interface, memory card, easyNet, easyLink Yes
Rated operational voltage U
e
V
DC
24
On 0 signal U
e
V
DC
< 5.0 (I1 - I4) < 8.0 (I11, I12)
On 1 signal U
e
V
DC
>15.0 (I1 - I4) > 8.0 (I11, I12)
Input current on 1 signal
I11, I12 mA 2.2 (at 24 V DC)
Delay time from 0 to 1 ms
Debounce ON ms 20
Debounce OFF ms Normally 0.1 (I1 - I4), Normally 0.25 (I11 - I12)
Delay time from 1 to 0 ms
Debounce ON ms 20
Debounce OFF ms Normally 0.1 (I1 - I4), normally 0.2 (I11, I12)
Cable length (unscreened) m 100
Frequency counter
Quantity 4 (I1, I2, I3, I4)
Counter frequency kHz < 3
Pulse shape Square
Incremental counter
Quantity 2 (I1 + I2, I3 + I4)
Counter frequency kHz
3
Pulse shape Square
Signal offset 90°
Rapid counter inputs
Number 4 (I1, I2, I3, I4)
Counter frequency kHz < 3
Pulse shape Square
Cable length, screened m < 20
Analog�inputs
Potential isolation
From power supply No
From the digital inputs No
From the outputs Yes
for Program code Yes
Input type DC voltage
Signal range V
DC
0 - 10