Datasheet
03/22/2012 HPL-ED2011 V2.0 EN (UX111) 1 / 5
I/O�MFD�24VDC,Trans.,�2I�x�PT100
Part�no. MFD-TP12-PT-B
Article�no. 106043
Program
Configurable temperature range
Supply voltage 24 V DC
Inputs
Digital 6
of which can be used as analog 2
Pt100 2
Outputs
Transistor 4
Temperature range
Temperature detector -200…+200 °C
0…+850 °C
Approbationen
UL approval Yes
CSA approval Yes
Product Standards IEC/EN see Technical Data; UL 508; CSA C22.2 No. 142-M1987; CSA C22.2 No. 213-
M1987; CE marking
UL File No. E135462
UL CCN NRAQ
CSA File No. 012528
CSA Class No. 2252-01 + 2258-02
NA Certification UL listed, CSA certified
Degree of Protection IEC: IP20, UL/CSA Type: -
General
Standards EN 61000-6-1/-2/-3/-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D) mm 89 x 90 x 25 (installed)
Weight kg 0.14
Mounting Fitted into the power supply unit.
Terminal�capacities
Solid
mm
2
0.2⁄4 (AWG 24 - 12)
Flexible with ferrule
mm
2
0.2⁄2.5 (AWG 24 - 12)
Standard screwdriver mm 3.5 x 0.6
Climatic�environmental�conditions
Operating ambient temperature °C -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2
Condensation Take appropriate measures to prevent condensation
Storage °C - 40 - 70
Relative humidity, non-condensing (IEC/EN 60068-2-30) % 5 - 95
Air pressure (operation) hPa 795 - 1080
Ambient�conditions,�mechanical
Pollution degree 2
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 60068-2-6) Hz
Constant amplitude 0.15 mm Hz 10 - 57
Constant acceleration 2 g Hz 57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15
g/11 ms
Impacts 18
Drop to IEC/EN 60068-2-31 Drop
height
mm 50
Free fall, packaged (IEC/EN 60068-2-32) m 1
Mounting position Vertical or horizontal
Electromagnetic�compatibility�(EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD) kV
Air discharge kV 8
Contact discharge kV 6