Datasheet

Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature -25 - 70
Degree of Protection IP65
Mounting position As required
Mechanical shock resistance to IEC 60068-2-27 Half-
sinusoidal
shock 20 ms
g > 10
Vibration resistance acc. to IEC/EN 60068-2-6 Amplitude 1
mm
Hz 36
lifespan Operations
x 10
6
1
Terminal capacities
mm
2
Solid
mm
2
1 x (0.75 - 2.5)
2 x (0.75 - 1.5)
Flexible with ferrules to DIN 46228
mm
2
1 x (0.5 - 1.5)
Terminations Tunnel terminal
Terminal screw M3
Tightening torque of terminal screw Nm 0.5
Contacts/switching capacity
Rated impulse withstand voltage U
imp
V AC 4000
Rated insulation voltage U
i
V 400
Overvoltage category/pollution degree III/3
Max. short-circuit protective device
Fuseless Type PKZM0-6,3
Fuse gG/gL A 10
AC-15
Rated operational current
230 V, 50/60Hz A 2
DC-13
Rated operational current
24 V A 2
110 V A 0.25
Rated frequency f Hz 50
Design verification as per IEC/EN 61439
Technical data for design verification
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Pressure switch (EC000243)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Monitoring equipment (low-voltage switch technology) / Pressure monitoring equipment
(ecl@ss10.0.1-27-37-18-14 [AKF108014])
Suitable as guard Yes
Suitable as 2-point controller Yes
Suitable as limiter No
Max. operation pressure hPa 7000
Engaging pressure bar 0 - 4.2
Initial setting hPa 0 - 0
Switch off pressure bar 0 - 4.5
End setting hPa 0 - 0
Pressure-switching differential bar 0
Max. test pressure bar 32
Bursting pressure bar 90
Medium temperature °C 25 - 80
Connection Inner thread gas cylindrical (BSPP)
Thread size 1/2 inch