Specifications
CA08101001E For more information visit: www.eaton.com
16-57
Transfer Switches
February 2007
16
Transfer Switch Equipment
Appendix C — Transfer Switches — Transient Voltage Surge Suppression Device
Appendix C
Transient Voltage Surge Suppression Device
Figure 16-20. Visor OEM 100, 100 and 200 kA Technical Data
Technical Data
Table 16-50. Visor Series — General Parameters
Remote display cables only for use on configuration B and Z models.
Description OEM Visor
kA/Mode 50 – 250
kA/Phase 100 – 500
Split-Phase System 240
L, L, N, G
Wye System Voltages 120/208
277/480
347/600
L, L, L, N, G
Delta System Voltages 240
480
600
L, L, L, G
International System
Voltages
127/220Y
230/400
L, L, L, N, G
Mexico, other
Monitoring AdVisor
SuperVisor
NetVisor
Mounting Panelboards (PRL1A, 2A, 3A, 4)
Remote Monitor Device Panel (Switchboard, Switchgear, Busway)
MCC Version
Remote Display Cables
Ribbon Cable
DB15 600 V Class Cable
3 and 6 feet (0.9 and 1.8 m)
8 and 16 feet (2.4 and 4.9 m)
Temperature
Storage
Operation
-40ºC to +60ºC
-20ºC to +60ºC
Humidity (Relative) 5 – 95%
Warranty 10 years
Certifications/Listing UL 1449 2nd Edition, CSA 22.2, UL 1283.
Standards and Certifications
■ All Visor Series units have been tested
by UL and meet the requirements
under UL 1449 2nd Edition for surge
suppression devices.
■ All Visor Series units have been
tested as per NEMA LS-1 and ANSI/
IEEE C62.45.
■ Category A3 Ringwave (6 kV open
circuit, 200 A short circuit current
at 100 kHz).
■ Category B3 Ringwave (6 kV open
circuit, 500 A short circuit current
at 100 kHz).
■ Category C1 Combination Wave
(6 kV 1.2/50us open circuits, 3 kA
8/20us short circuit current).
■ Category C3 Combination Wave
(20 kV 1.2/50us open circuits, 10 kA
8/20us short circuit current).
■ UL 1020 (standard for safety for
thermal cutoffs for use in electrical
appliances and components).
■ UL 1283 listed for EMI/RFI noise
attenuation filtering (50 db at
100 kHz).
■ CSA C22.2.