Specifications

CA08101001E For more information visit: www.eaton.com
16-57
Transfer Switches
February 2007
16
Transfer Switch Equipment
Appendix C — Transfer Switches — Transient Voltage Surge Suppression Device
Appendix C
Transient Voltage Surge Suppression Device
Figure 16-20. Visor OEM 100, 100 and 200 kA Technical Data
Technical Data
Table 16-50. Visor Series — General Parameters
Remote display cables only for use on configuration B and Z models.
Description OEM Visor
kA/Mode 50 – 250
kA/Phase 100 – 500
Split-Phase System 240
L, L, N, G
Wye System Voltages 120/208
277/480
347/600
L, L, L, N, G
Delta System Voltages 240
480
600
L, L, L, G
International System
Voltages
127/220Y
230/400
L, L, L, N, G
Mexico, other
Monitoring AdVisor
SuperVisor
NetVisor
Mounting Panelboards (PRL1A, 2A, 3A, 4)
Remote Monitor Device Panel (Switchboard, Switchgear, Busway)
MCC Version
Remote Display Cables
Ribbon Cable
DB15 600 V Class Cable
3 and 6 feet (0.9 and 1.8 m)
8 and 16 feet (2.4 and 4.9 m)
Temperature
Storage
Operation
-40ºC to +60ºC
-20ºC to +60ºC
Humidity (Relative) 5 – 95%
Warranty 10 years
Certifications/Listing UL 1449 2nd Edition, CSA 22.2, UL 1283.
Standards and Certifications
All Visor Series units have been tested
by UL and meet the requirements
under UL 1449 2nd Edition for surge
suppression devices.
All Visor Series units have been
tested as per NEMA LS-1 and ANSI/
IEEE C62.45.
Category A3 Ringwave (6 kV open
circuit, 200 A short circuit current
at 100 kHz).
Category B3 Ringwave (6 kV open
circuit, 500 A short circuit current
at 100 kHz).
Category C1 Combination Wave
(6 kV 1.2/50us open circuits, 3 kA
8/20us short circuit current).
Category C3 Combination Wave
(20 kV 1.2/50us open circuits, 10 kA
8/20us short circuit current).
UL 1020 (standard for safety for
thermal cutoffs for use in electrical
appliances and components).
UL 1283 listed for EMI/RFI noise
attenuation filtering (50 db at
100 kHz).
CSA C22.2.