Specifications

February 2007
CA08101001E For more information visit: www.eaton.com
16-53
Transfer Switches
16
Transfer Switch Equipment
Transfer Switch — Optional Components
Transient Voltage Surge Suppression
Eaton's Clipper Power System —
Visor series transient voltage surge
suppression (TVSS) components can
be integrated into any closed transi-
tion soft load switch. Surge current
ratings 100 kA, 160 kA and 200 kA per
phase provide a range of cost effective
facility-wide protection solutions. Status
indication on each phase is standard
with any TVSS option. Metering and
communication capabilities are also
available. See Appendix C for details.
Communications
Optional communication capability via
Communication Gateway is available
allowing remote data access, control,
programming, system interface and
dispatch.
System Interface
A system control panel provides user-
friendly interface to the closed transi-
tion soft load controller, allowing oper-
ators to easily monitor the switching
devices position and manually test
generator and the system operations.
Switching Devices Status Lights
Source 1 Open (Green).
Source 1 Closed (Red).
Source 1 Trip (Amber).
Source 2 Open (Green).
Source 2 Closed (Red).
Source 2 Trip (Amber).
Front Panel Control Switches and Lights
The combination of the following pilot
devices can be implemented on the unit:
AUTO/TEST Switch.
SYSTEM TEST Switch.
TEST MODE Switch.
ALARM SILENCE Switch.
READY FOR OPERATION Lamp (White)
— verifies the ATC-5000 status.
Optional Intergral Overcurrent Protection
Capability
For service entrance applications, Digitrip
microprocessor-based trip units can be
integrated into the power switching
devices. This eliminates the need for
the separate upstream protective
device, saving installation cost and
space. Available with various combi-
nations of Long, Short, Instantaneous
and Ground Fault Protection, Digitrips
can communicate with Eaton’s IMPACC
and PowerNet Power Management
Systems.
Optional On-board 24 Vdc Power Supply
On-board 24 Vdc power supply circuit,
consisting of two (2) 12 Vdc gel-cell UPS
type batteries and battery charger, is
available on the unit to provide dc
control power to soft load transfer
switch components. Engine battery
can be connected in the “best battery”
circuit as well, further improving the
system’s reliability.
Transfer Switch — Optional Components
Table 16-47. Options
Description
Service Entrance Rating
16N Overcurrent Protection — Normal
16E Overcurrent Protection — Emergency
16B Overcurrent Protection — Both
37A Service Entrance
37B Service Entrance with Ground Fault
Metering
18O IQ Analyzer — Normal
18P IQ Analyzer — Emergency
18Q IQ Analyzer — N/E Selectable
18U IQ Analyzer — Load
Plant Exerciser
23J Automatic 24 Hours/7 Days Selectable Load/No Load
Expanded Controller I/O
25A Additional Discrete and Analog I/O for Genset Control and Monitoring
Space Heater and Thermostat
41C 400 W Heater with Thermostat
Surge Protection
51M4B Engine Control (24 Vdc) Surge Device
51NA1 100 kA Surge Device with AdVisor Source 1
51NS1 100 kA Surge Device with SuperVisor Source 1
51NN1 100 kA Surge Device with NetVisor Source 1
51QA1 160 kA Surge Device with AdVisor Source 1
51QS1 160 kA Surge Device with SuperVisor Source 1
51QN1 160 kA Surge Device with NetVisor Source 1
51SA1 200 kA Surge Device with AdVisor Source 1
51SS1 200 kA Surge Device with SuperVisor Source 1
51SN1 200 kA Surge Device with NetVisor Source 1
On-Board 24 Vdc Power Supply
24C Battery Charger and Gell-Cell Batteries
Protective Devices
53A Beckwith M-3410A
53B Schweitzer SEL-547
53C Basler BE1-951
53D Beckwith M-3520
53E Schweitzer SEL-351
53F Basler BE1-IPS100
Communication
54B External Communication Gateway
54C Serial Modbus Over Ethernet
Field Start-up
56A 2-Day Start-up (Includes 1 Day for Travel)