Datasheet

03/18/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 3
at 5 V DC/1 mA H
F
Fault
probability
< 5 x 10
-6
, < 1 failure in 5 x 10
6
operations
Max. short-circuit protective device
Fuseless Type PKZM0-10/FAZ-B6/1
Fuse gG/gL A 10
Switching�capacity
Rated operational current I
e
A
AC-15
115 V I
e
A 6
230 V I
e
A 6
400 V I
e
A 4
500 V I
e
A 2
DC-13
24 V I
e
A 3
42 V I
e
A 1.7
60 V I
e
A 1.2
110 V I
e
A 0.8
220 V I
e
A 0.3
Lifespan, electrical
AC-15
230 V/0.5 A Operations x
10
6
1.6
230 V/1.0 A Operations x
10
6
1
230 V/3.0 A Operations x
10
6
0.7
DV-13
12 V/2.8 A Operations x
10
6
1.2
Indoor and protected outdoor installation
Technical�data�according�to�ETIM�4.0
Mounting diameter mm 22
Number of installable devices 4
CAD-Data
Product standards CAD data: http://eaton-moeller.partcommunity.com
Dimensions