Datasheet

Contacts/switching capacity
Rated impulse withstand voltage U
imp
V AC 6000
Rated insulation voltage U
i
V 500
Rated operational current I
e
A
AC-15
24 V I
e
A 6
220 V 230 V 240 V I
e
A 6
380 V 400 V 415 V I
e
A 4
DC-13
24 V I
e
A 3
110 V I
e
A 0.8
220 V I
e
A 0.3
Supply frequency Hz max. 400
Short-circuit rating to IEC/EN 60947-5-1
max. fuse A gG/gL 6
Repetition accuracy mm 0.02
Rated conditional short-circuit current kA 1
Mechanical variables
Lifespan, mechanical Operations
x 10
6
1
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
Standard-action contact g 25
Operating frequency Operations/h ≦ 1800
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation I
n
A 6
Heat dissipation per pole, current-dependent P
vid
W 0.13
Equipment heat dissipation, current-dependent P
vid
W 0
Static heat dissipation, non-current-dependent P
vs
W 0
Heat dissipation capacity P
diss
W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
02/07/2019 Eaton 106852 ED2019 V52.0 EN 2 / 4