User manual

LCX9000 Liquid-Cooled Drives User Manual
3-10 For more information visit: www.eaton.com
MN04005001E
September 2007
Table 3-10: Fuse Sizes for LCX9000 AFE Units (525 – 690V)
Note: SHT fuses can be assembled into DIN fuse base of the corresponding size.
Cable Installation Instructions
1. Before starting the installation, check that none of the components of the drive is live.
2. LCX9000 Liquid-Cooled drive must always be installed in an enclosure, a separate
cubicle or an electrical room.
Always use a jib crane or similar lifting device to lift the drive. For safe and appropriate
lifting, see Page 2-1.
3. Place the motor cables far enough from other cables:
Avoid placing the motor cables in long parallel lines with other cables.
If the motor cables run in parallel with other cables, note the minimum distances
between the motor cables and other cables given in table below.
The given distances also apply between the motor cables and signal cables of other
systems.
The maximum length of the motor cables is 984 feet (300m).
The motor cables should cross other cables at an angle of 90 degrees.
4. If cable insulation checks are needed, see Page 3-14.
Chassis
Catalog
Number
I
th
(A)
DIN43620 DIN43653 (110 mm)
Fuse
U
n
(V)
Fuse
I
n
(A)
Qty. of
Fuses/
Phase 3aR Fuse
Fuse
Size aR Fuse
Fuse
Size
CH61 LCX170A0-5 170 170M4199 1SHT 170M4985 1TN/110 1250 400 1
LCX0208A0-5 208 170M4199 1SHT 170M4985 1TN/110 1250 400 1
LCX0261A0-5 261 170M4199 1SHT 170M4985 1TN/110 1250 400 1
CH62 LCX0325A0-5 325 170M6305 3SHT 170M8636 3TN/110 1250 700 1
LCX0385A0-5 385 170M6305 3SHT 170M8636 3TN/110 1250 700 1
LCX0416A0-5 416 170M6305 3SHT 170M8636 3TN/110 1250 700 1
LCX0460A0-5 460 170M6277 3SHT 170M8639 3TN/110 1100 1000 1
LCX0502A0-5 502 170M6277 3SHT 170M8639 3TN/110 1100 1000 1
CH63 LCX0590A0-5 590 170M6277 3SHT 170M8639 3TN/110 1100 1000 1
LCX0650A0-5 650 170M6305 3SHT 170M8636 3TN/110 1250 700 2
LCX0750A0-5 750 170M6305 3SHT 170M8636 3TN/110 1250 700 2
CH64 LCX0820A0-5 820 170M6305 3SHT 170M8636 3TN/110 1250 700 2
LCX0920A0-5 920 170M6277 3SHT 170M8639 3TN/110 1100 1000 2
170M8639 3TN/110 1100 1000 2
170M8639 3TN/110 1100 1000 2
LCXH13A0-5 1300 170M6305 3SHT 170M8636 3TN/110 1250 700 3
LCXH15A0-5 1500 170M6277 3SHT 170M8639 3TN/110 1100 1000 3
Distance between
Parallel Running
Cables in Feet (m)
Shielded
Cable
in Feet (m)
10 (.3) 164 (50)
3.3 (1.0) 656 (200)