User manual

LCX9000 Liquid-Cooled Drives User Manual
1-10 For more information visit: www.eaton.com
MN04005001E
September 2007
DC Units
Table 1-4: Power Ratings and Dimensions of Liquid-Cooled Inverter Unit, Supply
Voltage 540 – 675V DC
Catalog
Number
Drive Output
Power Loss
c/a/T
(kW) Chassis
Current Motor Output Power
Thermal
I
th
(A)
Rated
Cont. I
L
(A)
Rated
Cont. I
H
(A)
Optimum
Motor at I
th
400V (kW)
Optimum
Motor at I
th
500V (kW)
LCX016A0-4 16 15 11 7.5 11 0.4/0.2/0.6 CH3
LCX022A0-4 22 20 15 11 15 0.5/0.2/0.7 CH3
LCX031A0-4 31 28 21 15 18.5 0.7/0.2/0.9 CH3
LCX038A0-4 38 35 25 18.5 22 0.8/0.2/1.0 CH3
LCX045A0-4 45 41 30 22 30 1.0/0.3/1.3 CH3
LCX061A0-4 61 55 41 30 37 1.3/0.3/1.5 CH3
LCX072A0-4 72 65 48 37 45 1.2/0.3/1.5 CH4
LCX087A0-4 87 79 58 45 55 1.5/0.3/1.8 CH4
LCX105A0-4 105 95 70 55 75 1.8/0.3/2.1 CH4
LCX140A0-4 140 127 93 75 90 2.3/0.3/2.6 CH4
LCX168A0-4 168 153 112 90 110 2.5/0.3/2.8 CH5
LCX208A0-4 208 186 137 110 132 3.0/0.4/3.4 CH5
LCX261A0-4 261 237 174 132 160 4.0/0.4/4.4 CH5
LCX300A0-4 300 273 200 160 200 4.5/0.4/4.9 CH61
LCX385A0-4 385 350 257 200 250 5.5/0.5/6.0 CH61
LCX460A0-4 460 418 307 250 315 5.5/0.5/6.0 CH62
LCX520A0-4 520 473 347 250 355 6.5/0.5/7.0 CH62
LCX590A0-4 590 536 393 315 400 7.5/0.6/8.1 CH62
LCX650A0-4 650 591 433 355 450 8.5/0.6/9.1 CH62
LCX730A0-4 730 664 487 400 500 10.0/0.7/10.7 CH62
LCX820A0-4 820 745 547 450 560 12.5/0.8/13.3 CH63
LCX920A0-4 920 836 613 500 600 14.4/0.9/15.3 CH63
LCXH10A0-4 1030 936 687 560 700 16.5/1.0/17.5 CH63
LCXH11A0-4 1150 1045 766 600 750 18.4/1.1/19.5 CH63
LCXH13A0-4 1370 1245 913 700 900 15.5/1.0/16.5 CH64
LCXH16A0-4 1640
1491 1093 900 1100 19.5/1.2/20.7 CH64
LCXH20A0-4 2060 1873 1373 1100 1400 26.5/1.5/28.0 CH64
LCXH23A0-4 2300 2091 1533 1250 1500 29.6/1.7/31.3 CH64
LCXH24A0-4 2470 2245 1647 1300 1600 36.0/2.0/38.0 2*CH64
LCXH29A0-4 2950 2681 1967 1550 1950 39.0/2.4/41.4 2*CH64
LCXH37A0-4 3710 3372 2473 1950 2450 48.0/2.7/50.7 2*CH64
LCXH41A0-4 4140 3763 2760 2150 2700 53.0/3.0/66.0 2*CH64