Technical data

June 2008
CA08102001E For more information visit: www.eaton.com
40-91
Adjustable Frequency Drives
40
SVX9000
Enclosed Drives
Modbus RTU Network Communications
The Modbus Network Card OPTC2 is
used for connecting the 9000X Drive as
a slave on a Modbus network. The
interface is connected by a 9-pin DSUB
connector (female) and the baud rate
ranges from 300 to 19200 baud. Other
communication parameters include an
address range from 1 to 247; a parity of
None, Odd or Even; and the stop
bit is 1.
Profibus Network Communications
The Profibus Network Card OPTC3 is
used for connecting the 9000X Drive as
a slave on a Profibus-DP network. The
interface is connected by a 9-pin DSUB
connector (female). The baud rates
range from 9.6K baud to 12M baud,
and the addresses range from 1 to 127.
LonWorks Network Communications
The LonWorks Network Card OPTC4 is
used for connecting the 9000X Drive
on a LonWorks network. This interface
uses Standard Network Variable Types
(SNVT) as data types. The channel
connection is achieved using a
FTT-10A Free Topology transceiver
via a single twisted transfer cable. The
communication speed with LonWorks
is 78 kBits/s.
CanOpen (Slave) Communications
The CanOpen (Slave) Network Card
OPTC6 is used for connecting the
9000X Drive to a host system. Accord-
ing to ISO11898 standard cables to be
chosen for CAN bus should have a
nominal impedance of 120Ω, and
specific line delay of nominal 5 nS/m.
120Ω line termination resistors
required for installation.
DeviceNet Network Communications
The DeviceNet Network Card OPTC7
is used for connecting the 9000X Drive
on a DeviceNet Network. It includes a
5.08 mm pluggable connector. Trans-
fer method is via CAN using a 2-wire
twisted shielded cable with 2-wire bus
power cable and drain. The baud rates
used for communication include 125K
baud, 250K baud and 500K baud.
Johnson Controls Metasys™ N2 Network
Communications
The OPTC2 fieldbus board provides
communication between the 9000X
Drive and a Johnson Controls
Metasys™ N2 network. With this con-
nection, the drive can be controlled,
monitored and programmed from the
Metasys system. The N2 fieldbus is
available as a factory installed option
and as a field installable kit.
Modbus/TCP Network Communications
The Modbus/TCP Network Card OPTCI
is used for connecting the 9000X Drive
to Ethernet networks utilizing Modbus
protocol. It includes an RJ-45 plugga-
ble connector. This interface provides
a selection of standard and custom
register values to communicate
drive parameters. The board supports
10 Mbps and 100 Mbps communica-
tion speeds. The IP address of the
board is configurable over Ethernet
using a supplied software tool.
BACnet Network Communications
The BACnet Network Card OPTCJ
is used for connecting the 9000X Drive
to BACnet networks. It includes a
5.08 mm pluggable connector. Data
transfer is Master-Slave/Token
Passing (MS/TP) RS-485. This interface
uses a collection of 30 Binary Value
Objects (BVOs) and 35 Analog Value
Objects (AVOs) to communicate drive
parameters. The card supports 9.6,
19.2 and 38.4 Kbaud communication
speeds and supports network
addresses 1 – 127.
Ethernet/IP Network Communications
The Ethernet/IP Network Card OPTCK
is used for connecting the 9000X Drive
to Ethernet/Industrial Protocol net-
works. It includes an RJ-45 pluggable
connector. The interface uses CIP
objects to communicate drive
parameters (CIP is “Common Indus-
trial Protocol”, the same protocol used
by DeviceNet). The board supports 10
Mbps and 100 Mbps communication
speeds. The IP address of the board is
configurable by Static, BOOTP and
DHCP methods.
Table 40-128. I/O Specifications for the Control/Communication Options
SVX Conversion Kit
Table 40-129. SVX Conversion Kit Frame 4 – 7
Note: The kit consists of a flange kit, adapter plate(s), hardware, remote keypad kit and
SVX9000 decal.
Table 40-130. Conformal (Varnished) Coating
Adder — 208 – 240V, 380 – 500V
See catalog number description to order.
Description Specifications
Analog voltage, input 0 – ±10V, R
i
200 k
Analog current, input 0 (4) – 20 mA, R
i
= 250
Digital Input 24V: “0” 10V, “1” 18V, R
i
> 5 k
Aux. voltage 24V (±20%), max. 50 mA
Reference voltage 10V ±3%, max. 10 mA
Analog current, output
Analog voltage, output
0 (4) – 20 mA, R
L
= 500 k, resolution 10 bit, accuracy ±2%
0 (2) – 10V, R
L
1 k, resolution 10 bit, accuracy ±2%
Relay output
Max. switching voltage
Max. switching load
Max. continuous load
300V DC, 250V AC
8A/24V DC, .4A/300V DC, 2 kVA/250V AC
2A rms
Thermistor input R
trip
= 4.7 k
Encoder input 24V: “0” 10V, “1” 18V, R
i
= 2.2 k
5V: “0” 2V, “1” 3V, R
i
= 330
Frame Size Enclosure
Size
Catalog Number Delivery
Code
Price
U.S. $
FR4 0 OPTCON-SVXFR4-SZ00 FB10
FR4 1 OPTCON-SVXFR4-SZ01 FB10
FR5 0 OPTCON-SVXFR5-SZ00 FB10
FR5 1 OPTCON-SVXFR5-SZ01 FB10
FR6 1 OPTCON-SVXFR6-SZ01 FB10
FR6 2 OPTCON-SVXFR6-SZ02 FB10
FR7 2 OPTCON-SVXFR7-SZ02 FB10
Frame Delivery
Code
Adder
U.S. $
FR4
FR5
FR6
FR7
FR8
FP
FP
FP
FP
FP
FR9
FR10
FP
FP
FR11
FR12
FP
FP
FR13
FR14
FP
FP
Discount Symbol. . . . . . . . . . . . . . . . . . . . . . . . SS-2