Technical data
June 2008
40-282
For more information visit: www.eaton.com CA08102001E
Adjustable Frequency Drives
40
SPA9000/SPI9000/SPN9000
Features and Benefits
Table 40-394. Standard Features
Technical Data and Specifications
Table 40-395. Specifications
Feature SPI9000 SPA SPN
FR4, 6, 7 FR8 FI9 – FI14 FI9 – FI14 FI9
IP00 ●●●●
IP21 ●
Air cooling ●●●●●
Standard board ●●●●
Varnished board ●
Alphanumeric keypad ●●●●
EMC class T (EN 61800-3 for IT networks) ●●●●●
Safety CE / UL ●●●●●
Input choke ●
LCL filter ●
No integrated charging ●●
Integrated charging (DC side) ●● ●
Diode/thyristor rectifier ●
IGBT ●●●●
Description Specifications
Supply Connection
Input voltage U
in
(AC) Front End modules 380 – 500V AC / 525 – 690V AC -10% to +10%
Input voltage U
in
(DC) Inverter 465 – 800V DC / 640 – 1100V DC -0% to +0%, The waviness of the inverter supply voltage,
formed in rectification of the electric network’s alternating voltage in basic frequency,
must be less than 50V peak-to-peak
Output voltage U
out
(AC) Inverter 3 ~ 0 – U
in
/ 1.4
Output voltage U
out
(DC) Active Front End module 1.10 x 1.35 x U
in
(Factory default)
Output voltage U
out
(DC) Non-regenerative Front End module 1.35 x U
in
Ambient Conditions
Ambient operating temperature 14 (no frost) to 122°F (-10 to 50°C): I
H
14 (no frost) to 104°F (-10 to 40°C): I
L
Storage temperature -40 to 158°F (-40 to 70°C )
Relative humidity 0 to 95% RH, non-condensing, non-corrosive, no dripping water
Air quality:
– chemical vapors
– mechanical particles
IEC 721-3-3, unit in operation, class 3C2
IEC 721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 1000m
1% derating for each 100m above 1000m; max. 3000m
Vibration 5 – 150 Hz
EN50178/EN60068-2-6 Displacement amplitude 0.25 mm (peak) at 3 – 15.8 Hz
Max acceleration amplitude 1G at 15.8 – 150 Hz
Shock
EN50178, EN60068-2-27
UPS Drop Test (for applicable UPS weights)
Storage and shipping: max 15G, 11 mS (in package)
Cooling capacity required approximately 2%
Cooling air required FR4 41 cfm, FR6 250 cfm, FR7 250 cfm, FR8 383 cfm
FI9 677 cfm, FI10 824 cfm, FI12 1648 cfm, FI13 2472 cfm
Unit enclosure class FR4 – FR7 NEMA Type 1 (IP21); FR8, FI9 – FI14 Chassis (IP00)
EMC (at fault settings)
Immunity Fulfill all EMC immunity requirements
Safety
Approvals CE, UL, CUL, EN 61800-5-1 (2003), see unit nameplate for more detailed approvals
Control Connections
Analog input voltage 0 – 10V, R
i
= 200 kΩ, (-10V – 10V joystick control)
Resolution 0.1%, accuracy ±1%
Analog input current 0(4) – 20 mA, R
i
= 250Ω differential
Digital inputs 6, positive or negative logic; 18 – 30V DC