Technical Data and Specifications
Table 40-255. HVX9000 Specifications
Description Specification
Input Ratings
Input Voltage (V
in
) +10% / -15%
Input Frequency (f
in
) 50/60 Hz (variation up to 45 – 66 Hz)
Connection to Power Once per minute or less (typical
operation)
Short Circuit Withstand
Rating
100 kAIC
Output Ratings
Output Voltage 0 to V
in
Continuous Output
Current
Ambient temperature max. +104°F(+40°C)
Overload Current 110% (1 min./10 min.)
Output Frequency 0 to 320 Hz
Frequency Resolution .01 Hz
Control Characteristics
Control Method Frequency Control (V/f) Open Loop
Sensorless Vector Control
Switching Frequency Adjustable with Parameter 2.6.9
1 – 40 hp: 1 to 16 kHz; default 10 kHz
50 – 75 hp: 1 to 10 kHz; default 3.6 kHz
Frequency Reference Analog Input: Resolution .1% (10-bit),
accuracy ± 1%
Panel Reference: Resolution .01 Hz
Field Weakening Point 30 to 320 Hz
Acceleration Time 0 to 3000 sec.
Deceleration Time 0 to 3000 sec.
Braking Torque DC brake: 30% x T
n
(without brake option)
Ambient Conditions
Ambient Operating
Temperature
14°F (-10°C), no frost to 104°F (+40°C)
Storage Temperature -40°F (-40°C) to 158°F (70°C)
Relative Humidity 0 to 95% RH, noncondensing,
non-corrosive, no dripping water
Air Quality Chemical vapors: IEC 721-3-3, unit in
operation, class 3C2; Mechanical particles:
IEC 721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to
3280 ft. (1000m); 1% derating for each
328 ft. (100m) above 3280 ft. (1000m);
max. 9842 ft. (3000m)
Vibration EN 50178, EN 60068-2-6; 5 to 50 Hz,
Displacement amplitude 1 mm (peak) at
3 to 15.8 Hz, Max. acceleration amplitude
1G at 15.8 to 150 Hz
Shock EN 50178, EN 60068-2-27 UPS Drop test
(for applicable UPS weights) Storage and
shipping: max. 15G, 11 ms (in package)
Enclosure Class NEMA Type 1/IP21 or NEMA Type 12/IP54
Description Specification
Standards
Product IEC 61800-2
Safety UL 508C
EMC (at default settings) Immunity: Fulfills all EMC immunity
requirements; Emissions: EN 61800-3,
LEVEL H
Control Connections
Analog Input Voltage 0 to 10V, R = 200Ω differential (-10 to 10V
joystick control) Resolution .1%; accuracy
±1%
Analog Input Current 0(4) to 20 mA; R
i
- 250Ω differential
Digital Inputs (6) Positive or negative logic; 18 to 24V DC
Auxiliary Voltage +24V ±15%, max. 250 mA
Output Reference Voltage +10V +3%, max. load 10 mA
Analog Output 0(4) to 20 mA; R
L
max. 500Ω; Resolution
10 bit; Accuracy ±2%
Digital Outputs Open collector output, 50 mA/48V
Relay Outputs 2 programmable Form C relay outputs
Switching capacity: 24V DC / 8A,
250V AC / 8A, 125V DC / 0.4A
Protections
Overcurrent Protection Yes
Overvoltage Protection Yes
Undervoltage Protection Yes
Earth Fault Protection In case of earth fault in motor or motor
cable, only the frequency converter is
protected
Input Phase Supervision Trips if any of the input phases are
missing
Motor Phase Supervision Trips if any of the output phases are
missing
Overtemperature
Protection
Yes
Motor Overload
Protection
Yes
Motor Stall Protection Yes
Motor Underload
Protection
Yes
Short Circuit Protection Yes (Of the +24V and +10V Reference
Voltages)