Technical data

June 2008
CA08102001E For more information visit: www.eaton.com
40-113
Adjustable Frequency Drives
40
SVX9000
VFD Pump Panels
Technical Data and Specifications
Table 40-164. Specifications
Some horsepower units include dynamic braking chopper as
standard — refer to individual drive sections.
Table 40-165. Standard I/O Specifications
Feature Description 9000X Enclosed Products —
NEMA Type 12 or NEMA Type 3R
Primary Design Features
45 – 66 Hz Input Frequency Standard
Output: AC Volts Maximum Input Voltage Base
Output Frequency Range: Hz 0 – 320
Initial Output Current (I
H
) 250% for 2 seconds
Overload: 1 Minute (I
H
/I
L
) 150%/110%
Enclosure Space Heater Optional
Oversize Enclosure Standard
Output Contactor Optional
Bypass Motor Starter Optional
Listings UL, cUL
Protection Features
Incoming Line Fuses Optional
AC Input Circuit Disconnect Optional
Line Reactors Standard
Phase Rotation Insensitive Standard
EMI Filter Standard — Thru Frame 9
Input Phase Loss Protection Standard
Input Overvoltage Protection Standard
Line Surge Protection Standard
Output Short Circuit Protection Standard
Output Ground Fault Protection Standard
Output Phase Protection Standard
Overtemperature Protection Standard
DC Overvoltage Protection Standard
Drive Overload Protection Standard
Motor Overload Protection Standard
Programmer Software Optional
Local/Remote Keypad Standard
Keypad Lockout Standard
Fault Alarm Output Standard
Built-In Diagnostics Standard
Input/Output Interface Features
Setup Adjustment Provisions:
Remote Keypad/Display
Personal Computer
Standard
Standard
Operator Control Provisions:
Drive Mounted Keypad/Display
Remote Keypad/Display
Conventional Control Elements
Serial Communications
115V AC Control Circuit
Standard
Standard
Standard
Optional
Optional
Speed Setting Inputs:
Keypad
0 – 10V DC Potentiometer/
Voltage Signal
4 – 20 mA Isolated
4 – 20 mA Differential
Standard
Standard
Configurable
Configurable
Analog Outputs:
Speed/Frequency
Torque/Load/Current
Motor Voltage
Kilowatts
0 – 10V DC Signals
4 – 20 mA DC Signals
Isolated Signals
Standard
Programmable
Programmable
Programmable
Configurable w/Jumpers
Standard
Optional
Feature Description 9000X Enclosed Products —
NEMA Type 12 or NEMA Type 3R
Input/Output Interface Features (Continued)
Discrete Outputs:
Fault Alarm
Drive Running
Drive at Set Speed
Optional Parameters
Dry Contacts
Open Collector Outputs
Additional Discrete Outputs
Standard
Standard
Programmable
14
1 (2 Relays Form C)
1
Optional
Communications:
RS-232
RS-422/485
DeviceNet™
Modbus RTU
CanOpen (Slave)
Profibus-DP
Lonworks
®
Johnson Controls Metasys™ N2
Standard
Optional
Optional
Optional
Optional
Optional
Optional
Optional
Performance Features
Sensorless Vector Control Standard
Volts/Hertz Control Standard
IR and Slip Compensation Standard
Electronic Reversing Standard
Dynamic Braking Optional
DC Braking Standard
PID Setpoint Controller Programmable
Critical Speed Lockout Standard
Current (Torque) Limit Standard
Adjustable Acceleration/Deceleration Standard
Linear or S Curve Accel/Decel Standard
Jog at Preset Speed
Standard
Thread/Preset Speeds 7
Automatic Restart Selectable
Coasting Motor Start Standard
Coast or Ramp Stop Selection Standard
Elapsed Time Meter
Optional
Carrier Frequency Adjustment
1 – 16 kHz
Standard Conditions for Application and Service
Operating Ambient Temperature 0 – 40°C
Storage Temperature -40 – 60°C
Humidity (Maximum),
Non-condensing
95%
Altitude (Maximum without Derate) 3300 ft. (1000m)
Line Voltage Variation +10/-15%
Line Frequency Variation 45 – 66 Hz
Efficiency >96%
Power Factor (Displacement) .96
Description Specification
6 – Digital Input Programmable 24V: “0” 10V, “1” 18V,R
i
> 5 k
2 – Analog Input Configurable
w/Jumpers
Voltage: 0 – ±10V, R
i
> 200 k
Current: 0 (4) – 20 mA, R
i
= 250 k
2 – Digital Output Programmable Form C Relays 250V AC 2 Amp or
30V DC2 Amp resistive
1 – Digital Output Programmable Open collector 48V DC 50 mA
1 – Analog Output Programmable
Configurable w/Jumper
0 – 20 mA, impedance 500 ohms,
resolution 106 ±3%