Specifications

Series SAFEPATH SP40S Voice Evacuation System
Voice Evacuation System
Indoor Communications
Available features and options:
Multi-Function Supervised Paging, Messaging, Background Music
Delivery and Emergency Voice Evacuation System
24 VDC battery backup
On-board digital voice messaging system with 8 standard
messages
Hand-held microphone and power supply/battery charger
Expandable to 5280 watts
Contact closure message activation
40 Watts supervised audio power
Compatible with all Wheelock power supplies, speakers, strobes,
clusters, and high power speaker arrays
Approvals: UL, CSMF, MEA, FM, Tested to CAN/ULC-S527,
2nd Edition*
*Evaluated by FM Approvals, a Standards Council of Canada (SCC)
accredited testing and certifiation organization, in accordance with
Canadian Codes and Standards
Model Number Order Code Description
SP40S 9929 Single channel system with 40 watts of supervised audio power and 2 amps of supervised
24 VDC synchronized strobe power and 8 standard messages. (Batteries not included, 2
required.) Red Enclosure.
SP40S-B 9935 Same as above but with black enclosure
AM-SP40S-SMK 9937 SP40S After Market 8 Message Standard Message Kit
AM-SP40S-PMK 9938 SP40S After Market 8 Message Programmed Message Kit
SP-COA 9908 C.O. Port Adapter for the SP40S
Recommended 24 VDC Power Supply is Wheelock RPS-2406 (Order Code 3770)
Audio/Technical Specifications
Switch mode, Class D amplifier (40 Watts)
Speaker Outputs 25V or 70.7V power limited
Frequency Response Voice: 275 Hz - 6.5 kHz
BGM: 100 Hz - 15 kHz
Meets UL Voice Evacuation Requirements
of 800 - 2800 Hz
Signal to Noise Ratio Better than 65 dB
Dynamic Range Better than 65 dB
Total Harmonic Distortion Less than 2%
Stand by Current Draw 130 mA
Alarm Current Draw 4.7 amps
16.27
21.22
6.06
EATON Voice Evacuation/Mass Notification www.coopernotification.com
63