Datasheet

Technical Specification
Operation
Supply Voltage
Range
19 to 60Vdc
Operating Range -10 to +70 °C [14 to 158 °F]
Input/Output
with IOBGP-00
Analog inputs Current sensor (3), Bus voltage (1), Temperature (2)
Digital inputs 4 Internal (pre-defined), 6 external (user-defined)
LVD contactor
outputs
2
Relay outputs 6 Voltage free, NO-C-NC, 0.5A @ 100VDC
Screw terminal block, 0.5mm
2
- 2.0mm
2
conductors
Communications
Interfaces
Physical RS232
Software S3P, MII
Management
software
DCTools configuration / local management software.
Power Xpert remote management software.
User Interface
Display Back-lit dot matrix LCD 128 x 128 pixel
Adjustable viewing angle
Keypad 4 keys
Language
Options
English: Standard
Other languages by arrangement.
Indicators Power on, Critical/major alarm, Minor alarm
Mechanical
Dimensions
H,W,D
SC100: 133.5mm (3U), 44.5mm, 60mm
IOBGP: 106mm, 175mm, 18mm
Mounting SC100: rectifier slot or flush panel mount
Orientation: vertical or horizontal
IOBGP: panel mount
Datalogging
Event Log 100 records
Options
Modem
communications
PSTN or GSM. Requires external modem.
Certifications
China MII
North America FCC Verification, IC
Europe CE
Australia /
New Zealand
C-tick
In the interests of continual product improvement all specifications are subject
to change without notice.
Internet: www.eaton.com/dcpower
Email: dc.info@eaton.com
Eaton, CellSure, SiteSure, DCTools and
Power Xpert are trade names, trademarks,
and/or service marks of Eaton Corporation
or its subsidiaries and affiliates. All other
trademarks are property of their respective
owners.
© 2009 Eaton Corporation
All Rights Reserved
SC100/IOBGP D