Datasheet
Technical Specification
Figure 1: 12V/7Ah Battery Capacity
*Battery times are approximate and vary depending
on factors such as:
- battery type
- load configuration
- battery charge
- battery age and temperature.
Country/Region Product Variance
Standard Product
MPS12-30 - Micro Power Solution, 12V, 30Watt, Includes Battery. AC
cordset not included.
United Kingdom
MPS12-30-UK - Micro Power Solution, 12V, 30Watt, Includes Battery
and UK 3pin cordset.
European Union
MPS12-30-EU - Micro Power Solution, 12V, 30Watt, Includes Battery
and Schucko cordset.
Australia and New Zealand
MPS12-30-ANZ - Micro Power Solution, 12V, 30Watt, Includes Battery
and Australia/New Zealand cordset.
North America
MPS12-30-NA - Micro Power Solution, 12V, 30Watt, Includes Battery
and North America cordset.
Brief Technical Specifications
AC Supply
Input range: 80-260Vac
Input frequency Range: 45-65Hz
Inlet: IEC inlet
DC Output
Nominal voltage:
Output Voltage Range:
Tolerance:
Output Protection:
Output power (max.): 30W
12VDC
10.5 – 13.8VDC
10.5V (-0.2V,+0.25V)
13.8V (-0.35V, +0.15V)
80%
10Amps fuse soldered on PCB
Battery
Typical type/rating: 12V/7Ah (see figure 1)
Discharge prevention: 10.5V ± 0.5V
Rated charging voltage: 13.7V ± 0.25V
Recharge time (internal batter): 4 hours to 90%
load after complete discharge.
Charge current: 2.5A maximum
Hot swappable
LED Indicator
AC mode: green LED continuous
Backup mode: yellow LED continuous
Battery low: yellow LED flashing
Battery replace: red LED flashing
Battery missing: red LED continuous
Fault: red LED continuous
Battery self-test: green LED flashing
Audible Alarm
Battery mode: every 5 seconds
Battery low: every 1 second
Battery replace: every 2 seconds
Battery missing: continuous
Fault: continuous
Physical Specification
Weight of unit: 3.5kgs
Dimensions H, W, D: 358mm, 120mm, 85.6mm
Operating temperature: 0°C to 40°C
Operating humidity: 0% to 90%
Operating elevation: 0 to 3000m
Certifications
All products comply with international standards.
Europe: CE
In the interests of continual product improvement all specifications are subject
to change without notice. Performance ratings are valid with all other variables
at Nominal. Specifications guaranteed over rated operating range.
Typical Backup time
0
5
10
15
20
25
30
2 4 6 8 101214161820
Time (Hours
)
Load (Watts)
Internet: www.eaton.com/dcpower
Email: dc.info@eaton.com
Eaton, CellSure, SiteSure, DCTools and
Power Xpert are trade names, trademarks,
and/or service marks of Eaton Corporation
or its subsidiaries and affiliates. All other
trademarks are property of their respective
owners.
© 2010 Eaton Corporation
All Rights Reserved
MPS B