Datasheet
Technical Specification
System Interconnections
Commun-
ications
Screw terminals
Power Direct onto busbars
DC
Distribution
(Optional)*
Load Circuit
Breakers
20-way total
Single Width
Circuit
Breakers
Heinemann AMIR Series 5A, 10A, 20A, 30A, 40A, 50A,
70A, 80A, 100A.
Dual Width
Circuit
Breakers
Heinemann AMIP 120A, 150A, 200A,
Triple Width
Circuit
Breakers
Heinemann AMIP 250A,
*Power is feed to the optional DC distribution from a load circuit in the
Power Cabinet. See power system documentation for more details.
Batteries*
Type Front access VRLA
48V Batteries Up to 600Ahr per cabinet using four strings of 150Ahr
batteries.
24V Batteries: Up to 1200Ahr per cabinet using eight strings of
150Ahr batteries.
*Maximum of 6 battery cabinets added to the power cabinet per system
Mechanical
Dimensions
H, W, D
With rear cable
duct extension
H,W,D
2000mm [78.7”], 600mm [23.6”], 600mm [23.6”]
2000mm [78.7”], 600mm [23.6”], 750mm [29.6”]
Weight
DV2-EBC4-xxxx: 850kg [1870lb]. Typical maximum
with 4 x 48V/150Ah battery strings.
Operating
Temperature
Range
-25°C [-13°F] to 40°C [104°F]
Humidity <95% non-condensing
Altitude <2000m (6500’). Thermally de-rates above this altitude,
to a maximum altitude of 4000m
Certifications (Pending)
All products comply with international standards. Contact your local Eaton DC
representative for details on the specific product versions available with these
safety and EMC approvals:
North America:
UL Listed 1801, cUL, FCC
In the interests of continual product improvement all specifications are
subject to change without notice.
Internet: www.eaton.com/dcpower
Email: dc.info@eaton.com
Eaton, CellSure, SiteSure, DCTools and
PowerManager are trade names,
trademarks, and/or service marks of Eaton
Corporation or its subsidiaries and
affiliates. All other trademarks are property
of their respective owners.
© 2010 Eaton Corporation
All Rights Reserved
DV2-3G EBCUL A