Operation
Supply Voltage
Range
18 to 60Vdc
Operating Range
Standard: -10 to +50°C [14 to 122 °F]
Extended: -25 to 70°C [-13 to 158 °F]
Input/Output
Standard
Analog inputs
Current sensor (3), Bus voltage (1), Temperature
(2)
Digital inputs
4 Internal (pre-defined), 6 external (user-defined)
LVD contactor
outputs
2 with one IOBGP module
Up to 16 with additional IOBGP modules
Relay outputs
6 Voltage free, NO-C-NC, 0.1A @ 60VDC
Screwless terminal block, 0.5mm
2
- 2.0mm
2
conductors
Communications
Interfaces
Physical
Ethernet, USB and RS232
Software
IP, http, https (secure web), S3P, modbus, SMTP
(email)
Management
software
DCTools configuration / local management
software.
Power Xpert remote management software.
SNMP version V1, V2c or V3. Supports standard
Network Management System software including
HP OpenView Network Node Manager.
User Interface
Display
Back-lit color dot matrix LCD 160 x 128 pixel
Adjustable viewing angle
Keypad
6 keys
Language
Options
English: Standard
Spanish, German and Chinese available on
request.
Other language software upgrades by
arrangement.
Indicators
Power on, Critical/Major alarm, Minor alarm
Mechanical
Dimensions
H,W,D
SC200: 133.5mm (3U), 44.5mm, 70mm
IOBGP: 106mm, 175mm, 18mm
Mounting
SC200: rectifier slot or flush panel mount
Orientation: vertical or horizontal
IOBGP: panel mount
Datalogging
Event Log
10,000 records
Data Log
10,000 records
Options
Input/Output
With IOBSS module (SiteSure-3G):
Analog inputs: 48
Digital inputs: 108
Digital outputs: 32
Modem
communications
PSTN or GSM. Requires external modem.
Certifications
China
MII
North America
UL, FCC Verification, IC
Europe
CE
Australia /
New Zealand
C-tick
In the interests of continual product improvement all specifications are