Datasheet
Internet: www.eaton.com/dcpower
Email: dc.info@eaton.com
Eaton, CellSure, SiteSure, DCTools and
PowerManager are trade names,
trademarks, and/or service marks of Eaton
Corporation or its subsidiaries and
affiliates. All other trademarks are property
of their respective owners.
© 2011 Eaton Corporation. All Rights
Reserved. DV2-3G UL C
Input
AC Supply
Voltage*
AC Input
Frequency
North America:
3P 208Vac nominal
2P 240Vac nominal
Global:
3P + N 230/400Vac nominal
1P + N 230Vac nominal
50/60 Hz
System
Rectifier
Module*
APR24-3G
APR48-3G
APR48-ES
Nominal
Output
Voltage
24Vdc
48Vdc
48Vdc
Output
Voltage range
20–30Vdc
40–58Vdc
40–58Vdc
Max Number
of Rectifiers
10
20
20
Maximum DC
Power
†
14.4kW
36kW
40kW
Maximum
Load Current
500A
600A
600A
Efficiency
>91%
>92%
>96%
† Maximum DC power includes load and battery recharge.
Supervisory
Module
SC200
Commun-
ications
10 baseT Ethernet port, web server, SNMP agent
Batteries
Type: Front access VRLA
48V: Up to 600Ahr per cabinet using four strings of
150Ahr batteries.
24V: Up to 1200Ahr per cabinet using eight strings of
150Ahr batteries.
Extension
Battery
Cabinets
Up to six extension battery cabinets fitted with either
four strings of 48V or eight strings of 24V in each
cabinet
DC
Distribution
Load circuit
Breakers
20-way total
Single Width
Circuit
Breakers
Heinemann AMIR Series 5A, 10A, 20A,
30A, 40A, 50A, 70A, 80A, 100A
Dual Width
Circuit
Breakers
Heinemann AMIP 120A, 150A, 200A
Triple Width
Circuit
Breakers
Heinemann AMIP 250A
Battery Circuit
Breakers
Heinemann AM1P, 200A integrated into battery shelf
Low Volt
Disconnect
Options
1 x battery disconnect, 1 x 400A non-priority load (10
positions for non priority, 10 positions for priority).
Mechanical
Dimensions
H,W,D
With rear cable
duct extension
H,W,D
2000mm [78.7”], 600mm [23.6”], 600mm [23.6”]
2000mm [78.7”], 600mm [23.6”], 750mm [29.6”]
Weight
DV2-A20B-xxxx:
900kg [1980lb] typical maximum with 20 rectifier
modules and 4 x 48V/150Ah battery strings.
Environ-
mental
Operating
Temperature
Range
-25°C [-13°F] to 40°C [104°F]*
Humidity
<95% non-condensing
Altitude
<2000m (6500’). Thermally de-rates above this altitude,
to a maximum altitude of 4000m
Certifications
All products comply with International Standards. Contact your local
Eaton Power Quality representative for details on the specific product
versions available with these safety and EMC approvals:
North America:
UL Listed 1801, cUL, FCC
*Refer to rectifier specifications for more information.
System capacity will vary depending on number of rectifiers and batteries
selected.
In the interests of continual product improvement all specifications are