Chapter 5 Shutdown
The Eaton Intelligent Power Manager (IPM) provides local computer graceful shutdown when connected to a
UPS through either a Network Management Card, USB port or RS-232 port.
This shutdown feature can be enabled or disabled from the Se
ttings > System > Modules Settings selection
path.
NOTE Refer to the Eaton Intelligent Power Protector (IPP) User’s Guide for a detailed
description of the Shutdown feature.
NOTE When the Shutdown feature is enabled, the software displays a communication
error until the Power Source is correctly configured as described in “Shutdown
Configuration.
Shutdown Configuration
To access the shutdown configuration options and verify that the Shutdown Module is enabled (administrator
access):
1. From the left-side Vie
ws panel of the Eaton IPM main interface window, select the Settings > Shutdown
menu item.The Shutdown page displays (see Figure 75).
The following configuration options are provided on the righ
t-side panel of the Shutdown page:
l
Edit power source
l
Edit shutdown configuration
l
Edit advanced shutdown criteria
l
Edit UPS configuration
l
Test access
l
Test shutdown
Figure 75. USB/Serial Power Source on Shutdown Page
To configure shutdown, perform the following actions:
1. Click the Ed
it Power Source button.
2. In the Power source field, select the UPS that powers the computer hosting the Eaton IPM.