User`s guide

Storage
124 Eaton Intelligent Power Manager (IPM) User’s Guide v1.40
P-164000289—Rev 2
When the ups_1 in on battery, the storage (netApp_1) will be shut off 300 seconds after the UPS loses
utility power.
5. Activate your user script (<Eaton install directory>configs\scripts\ netapp_shutdown.js) by the entering
the following:
UserScript. enabled: false, to UserScript. enabled: true
6. To activate the user trace (print information in the debug console and in the NetAppShutdown.log file), set
UserData.print = false
- to -
UserData.print = true.
7. Restart the service to apply the NetApp shutdown feature.
IMPORTANT
l
The access settings for <upsHostName> should be correctly set to enable communication with
the storage.
l
Because the Eaton IPM manages the shutdown of the NETAPP storage, it must be the last to
shut down. Therefore, the Eaton IPM shutdown timer setting must be greater than the
shutdown timer setting for the storage. (The IPM shutdown timer is configured from Settings >
Shutdown > Edit Shutdown Configuration.)
l
The first time the Secure Shell (SSH) function is called to shut down the NETAPP server, the
Eaton IPM automatically accepts the public key.