User`s guide
User Drivers
Eaton Intelligent Power Manager (IPM) User’s Guide v1.40 P-164000289—Rev 2 117
Figure 131. Other Data Panel
Source Object Name
This feature defines the name of the source object that you need to acquire. The following notes apply when
creating a source object name in the Rule editor dialog:
l
If the destination object name is indexed (for a standard object or a user-defined object), use “x” in the
source object name for the index position.
l
For an SNMP device, the source object name corresponds to the object ID (OID) name of the data to
acquire. The list is built from the device identification name which has been given. It corresponds to all OIDs
available under the OID root or the SysOID value.
l
For a NUT device, the source object name corresponds to the internal NUT object name.
If you provided a valid address in the check item of the driver, an interface is provided to help you to select the
appropriate source object from a list of value.
To define the source object name:
1. From the Rule editor dialog, click on the Br
owse source object name… button. The object list is built
automatically when the window opens.
NOTE You can pause the object list acquisition at any time using the Pause button.
2. The Res
tart button restarts the object list acquisition from the beginning.
3. The Cancel but
ton aborts the object list acquisition.
4. Select the appropriate object in the list and then click OK.
Conversion Rules
The following notes apply when defining the conversion rules in the Rule editor dialog:
l
The rules are evaluated in the order of the rule list.
l
Several rules can define the value of the same destination object.
l
Several rules can use the same source object.
Tabl e 17 provides a list of conversion rules.