User`s guide

Redundancy
104 Eaton Intelligent Power Manager (IPM) User’s Guide v1.40
P-164000289—Rev 2
Figure 122. Network Management Card Shutdown Parameters
Figure 123. UPS Shutdown and Restart Settings
Use Case #4
You want to have a shutdown when 10 min remain for the last UPS. In this case, each server can have an
individual shutdown duration, such as 10 min, 8 min, 3 min, and so forth.
l
The IPM default configuration is available from Settings > Shutdown > Edit Shutdown Configuration
(see Figure 124).
l
You must configure a shutdown duration of 10 min in the Eaton IPM.
NOTE This is the default configuration on the Network Management Card (refer to “Use
Case #3”).