User`s guide
Virtualization
Eaton Intelligent Power Manager (IPM) User’s Guide v1.40 P-164000289—Rev 2 95
2. In the Shutdown Settings panel on the right side of the page, select the applicable checkboxes to
configure the required parameters (see Figure 105 and Tabl e 10).
NOTE The shutdown settings that display vary depending on the node you select. In this
example, the node contains both remote maintenance mode feature parameters
and Eaton IPP shutdown parameters because the Eaton IPP performs the shutdown
locally.
Figure 107. Shutdown Settings for VM Host with
Table 11. Shutdown Settings with Eaton IPP on VM Host
Parameters Values Description
Remote Maintenance
Enabled or Disabled When enabled, it allows the server management
tool to move the VMs from this
server to another server in case of “UPS on battery state” and Maintenance Timer
elapsed).
Maintenance Timer
Type a value This represents the time elapsed “on
battery state” before the Eaton IPM script
changes the state of the host to maintenance mode. The “-1 second(s)” value
means that timer is disabled. See “Configuring Maintenance Mode and vMotion
with vCenter” on page 130 and “Configuring Maintenance Mode and Live
Migration with SCVMM” on page 133 for more information.
Power Source
IP address of UPS This parameter identifies the U
PS powering this server. This node must already
exist in Eaton IPM.
Load Segment
Master
Load Segment 1
Load Segment 2
This parameter identifies the U
PS load segment powering the server.
(NMC access) Login/
Pa
ssword
Type a value The Network Management Card Login/Password that allows IPP software to
control NMC shutdown sequence.
Master - Shutdown
Durat
ion
Type a value This server shutdown criteria defines the time needed for graceful host shutdown.
Master - Shutdown
Af
ter Value
Type a value This server shutdown criteria defines the time elapsed “on battery state” before
graceful Shutdown. This timer must be greater than the maintenance timer.
Power Source shutoff
Enabled or Disabled Typically Disabled. Enabled is used only for server conne
cted with UPS though
RS-232 or USB connection. Virtualization behavior requires Ethernet connectivity
(NMC card).
NOTE Shu
tdown settings that display vary depending on the node you select.